Table 52 Liebert NXL SA, SR, SN, MM, CD - Input <strong>and</strong> Holding (continued)<br />

Data Label<br />

ModuleList 1<br />

MMS Inter-Module Comm<br />

Status<br />

30554 1<br />

MMS Event Summary 30555 1<br />

MMS Module Inverter Status 30556 1<br />

MMS Module Output Voltage<br />

Status<br />

30557 1<br />

MMS Module Output Source 30558 1<br />

161<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - UPS Systems<br />

0 = Failed<br />

1 = Normal<br />

0 = None<br />

1 = Alarm<br />

2 = Fault<br />

0 = off<br />

1 = on<br />

0 = Fail<br />

1 = Marginal Low<br />

2 = Normal<br />

3 = Marginal High<br />

0 = Off<br />

1 = Normal<br />

2 = Bypass<br />

3 = Maintenance<br />

Bypass<br />

SCC, 1+N,<br />

1+1<br />

SCC, 1+N,<br />

1+1<br />

1+N, 1+1<br />

SCC, 1+N,<br />

1+1<br />

SCC, 1+N,<br />

1+1<br />

MMS Module Total kW Output 30559 1 Units : kW SCC<br />

MMS Module Total kVA Output 30560 1 Units : kVA SCC<br />

MMS Module DC Bus Voltage 30561 1 Units : VDC SCC<br />

MMS Module Battery Current 30562 1 Units : A DC SCC<br />

MMS Module Battery Time<br />

Remaining<br />

ModuleList 2<br />

30563 1 Units : min SCC<br />

MMS Inter-Module Comm<br />

Status<br />

30567 1<br />

0 = Failed<br />

1 = Normal<br />

SCC, 1+N,<br />

1+1<br />

MMS Event Summary 30568 1<br />

0 = None<br />

1 = Alarm<br />

2 = Fault<br />

SCC, 1+N,<br />

1+1<br />

MMS Module Inverter Status 30569 1 0 = off 1 = on 1+N, 1+1<br />

MMS Module Output Voltage<br />

Status<br />

Input<br />

Register<br />

Holding<br />

Register<br />

30570 1<br />

MMS Module Output Source 30571 1<br />

# of<br />

Regs Scale Units / Notes<br />

0 = Fail<br />

1 = Marginal Low<br />

2 = Normal<br />

3 = Marginal High<br />

0 = Off<br />

1 = Normal<br />

2 = Bypass<br />

3 = Maintenance<br />

Bypass<br />

NXL<br />

Types<br />

SCC, 1+N,<br />

1+1<br />

SCC, 1+N,<br />

1+1<br />

MMS Module Total kW Output 30572 1 Units : kW SCC<br />

MMS Module Total kVA Output 30573 1 Units : kVA SCC<br />

MMS Module DC Bus Voltage 30574 1 Units : VDC SCC<br />

MMS Module Battery Current 30575 1 Units : A DC SCC<br />

MMS Module Battery Time<br />

Remaining<br />

30576 1 Units : min SCC