Table 41 Liebert APM - Input <strong>and</strong> Holding (continued)<br />

136<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - UPS Systems<br />

Input Holding # of<br />

Data Description<br />

Register Register Reg. Scale Notes / Units<br />

System Output Voltage RMS A-B 30426 1 Units : VAC<br />

System Output Voltage RMS B-C 30427 1 Units : VAC<br />

System Output Voltage RMS C-A 30428 1 Units : VAC<br />

System Output Power Factor Phs A 30429 1<br />

Scale :<br />

x / 100<br />

System Output Power Factor Phs B 30430 1<br />

Scale :<br />

x / 100<br />

System Output Power Factor Phs C 30431 1<br />

Scale :<br />

x / 100<br />

System Output Pct Power Phase A 30432 1 Units : %<br />

System Output Pct Power Phase B 30433 1 Units : %<br />

System Output Pct Power Phase C 30434 1 Units : %<br />

MMS Output Apparent Power 30435 1 Units : kVA<br />

MMS Output Power 30436 1 Units : kW<br />

System Output Apparent Power 30437 1 Units : kVA<br />

System Output Power 30438 1 Units : kW<br />

Output Current Crest Factor Phs A 30439 1<br />

Scale :<br />

x / 10<br />

Output Current Crest Factor Phs B 30440 1<br />

Scale :<br />

x / 10<br />

Output Current Crest Factor Phs C<br />

System Status<br />

30441 1<br />

Scale :<br />

x / 10<br />

Inverter On/Off State 30445 1<br />

0 = off<br />

1 = on<br />

0 = Open<br />

Maintenance Bypass Breaker (MBB) 30446 1<br />

1 = Close<br />

2 = Not Installed<br />

1 = Other<br />

2 = Off<br />

3 = Normal<br />

UPS Output Source 30447 1<br />

4 = Bypass<br />

5 = Battery<br />

6 = Booster<br />

7 = Reducer<br />

1 = Normal Operation<br />

2 = StartUp<br />

System Status 30448 1<br />

8 = Normal with Warning<br />

16 = Normal with Alarm<br />

32 = Abnormal Operation<br />

ECO Mode Operation State<br />

System Configuration<br />

30449 1<br />

0 = disabled<br />

1 = enabled<br />

System Date <strong>and</strong> Time 39998 49998 2 Secs since Epoch(UTC)<br />

If the Scale column has a value for a Data Description, multiply the <strong>Modbus</strong> value by the value in the Scale column.