<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Power Distribution <strong>and</strong> Power Conditioning Products<br />

Table 36 Liebert EXC, Liebert FDC, Liebert FPC, Liebert RDC, Liebert PPC, Liebert RX - Input <strong>and</strong><br />

Holding (continued)<br />

Data Description<br />

Controller v4<br />

Liebert Products Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX<br />

Available Points<br />

Input<br />

Register<br />

Holding<br />

Register<br />

Panel 2 Position 2<br />

Breaker position 31607 - 1 - -<br />

Branch Current Phase 1 31608 - 1 10 A AC<br />

Branch Current Phase 2 31609 - 1 10 A AC<br />

Branch Current Phase 3 31610 - 1 10 A AC<br />

Branch Output Power (kW) 31611 - 1 1000 kW<br />

Output kW-Hrs 31612 - 2 1000 kWH<br />

Branch Output Power Factor 31614 - 1 100 -<br />

Branch Output Percent Load<br />

Panel 2 Position 84<br />

31615 - 1 - %<br />

Breaker position 32591 - 1 - -<br />

Branch Current Phase 1 32592 - 1 10 A AC<br />

Branch Current Phase 2 32593 - 1 10 A AC<br />

Branch Current Phase 3 32594 - 1 10 A AC<br />

Branch Output Power (kW) 32595 - 1 1000 kW<br />

Output kW-Hrs 32596 - 2 1000 kWH<br />

Branch Output Power Factor 32598 - 1 100 -<br />

Branch Output Percent Load<br />

Panel 3 Position 1<br />

32599 - 1 - %<br />

Breaker position 32603 - 1 - -<br />

Branch Current Phase 1 32604 - 1 10 A AC<br />

Branch Current Phase 2 32605 - 1 10 A AC<br />

Branch Current Phase 3 32606 - 1 10 A AC<br />

Branch Output Power (kW) 32607 - 1 1000 kW<br />

Output kW-Hrs 32608 - 2 1000 kWH<br />

Branch Output Power Factor 32610 - 1 100 -<br />

Branch Output Percent Load<br />

Panel 3 Position 2<br />

32611 - 1 - %<br />

Breaker position 32615 - 1 - -<br />

Branch Current Phase 1 32616 - 1 10 A AC<br />

Branch Current Phase 2 32617 - 1 10 A AC<br />

Branch Current Phase 3 32618 - 1 10 A AC<br />

Branch Output Power (kW) 32619 - 1 1000 kW<br />

Output kW-Hrs 32620 - 2 1000 kWH<br />

Branch Output Power Factor 32622 - 1 100 -<br />

Branch Output Percent Load 32623 - 1 - %<br />

121<br />

# of<br />

Reg. Scale Notes / Units