248<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Table 81 Liebert XDP, Liebert XDWP (XDP-W) - Binary Data (continued)<br />

Controller Liebert iCOM v4<br />

Data Description<br />

Compressors - Compressor Hours 1<br />

Object Type Instance<br />

Object<br />

Name Access Notes<br />

Compressor Hours Exceeded<br />

Compressors - Compressor Hours 2<br />

Binary_Value 472 5269_1_1 RD Active on Alarm<br />

Compressor Hours Exceeded<br />

Compressors - Compressor Hours 4<br />

Binary_Value 484 5269_1_2 RD Active on Alarm<br />

Compressor Hours Exceeded<br />

Compressors - T<strong>and</strong>em Pump Down 1<br />

Binary_Value 508 5269_1_4 RD Active on Alarm<br />

Compressor Pump Down Issue<br />

Compressors - T<strong>and</strong>em Pump Down 2<br />

Binary_Value 520 5146_1_1 RD Active on Alarm<br />

Compressor Pump Down Issue Binary_Value 532 5146_1_2 RD Active on Alarm<br />

Table 82 Liebert XDP, Liebert XDWP (XDP-W) - Analog Data<br />

Controller Liebert iCOM v4<br />

Data Description Object Type Instance<br />

Object<br />

Name Access Notes<br />

External Air<br />

Dew Point Temperature Analog_Value 1 4867_1 RD Units: deg C<br />

Dew Point Temperature Analog_Value 10001 4867_1 RD Units: deg F<br />

Minimum Room Temperature Set Point Analog_Value 2 4709_1 RW Units: deg C<br />

Minimum Room Temperature Set Point Analog_Value 10002 4709_1 RW Units: deg F<br />

Ext Air Sensor A Temperature Analog_Value 3 4594_1 RD Units: deg C<br />

Ext Air Sensor A Temperature Analog_Value 10003 4594_1 RD Units: deg F<br />

Ext Air Sensor A Humidity Analog_Value 4 4595_1 RD Units: % RH<br />

Ext Air Sensor A Dew Point Temp Analog_Value 5 4596_1 RD Units: deg C<br />

Ext Air Sensor A Dew Point Temp Analog_Value 10005 4596_1 RD Units: deg F<br />

Ext Air Sensor B Temperature Analog_Value 6 4597_1 RD Units: deg C<br />

Ext Air Sensor B Temperature Analog_Value 10006 4597_1 RD Units: deg F<br />

Ext Air Sensor B Humidity Analog_Value 7 4598_1 RD Units: % RH<br />

Ext Air Sensor B Dew Point Temp Analog_Value 8 4599_1 RD Units: deg C<br />

Ext Air Sensor B Dew Point Temp Analog_Value 10008 4599_1 RD Units: deg F<br />

Ext Air Over Temp Threshold Analog_Value 9 4600_1 RW Units: deg C<br />

Ext Air Over Temp Threshold Analog_Value 10009 4600_1 RW Units: deg F<br />

Ext Air Under Temp Threshold Analog_Value 10 4607_1 RW Units: deg C<br />

Ext Air Under Temp Threshold Analog_Value 10010 4607_1 RW Units: deg F<br />

Ext Dew Point Over Temp Threshold Analog_Value 11 4614_1 RW Units: deg C<br />

Ext Dew Point Over Temp Threshold<br />

Chilled Water<br />

Analog_Value 10011 4614_1 RW Units: deg F<br />

Supply Chilled Water Temperature Analog_Value 22 4624_1 RD Units: deg C<br />

Supply Chilled Water Temperature Analog_Value 10022 4624_1 RD Units: deg F<br />

Supply Chilled Water Over Temp Threshold Analog_Value 23 4625_1 RW Units: deg C<br />

Supply Chilled Water Over Temp Threshold Analog_Value 10023 4625_1 RW Units: deg F