Table 75 Liebert CRV - Multistate Data (continued)<br />

Controller Liebert iCOM v4<br />

Data Description Object Type Instance<br />

Customer Input 1 - Event Type Multistate_Value 177 4719_1 RW<br />

Customer Input 2 - Event Control Multistate_Value 178 5098_1 RW<br />

Customer Input 2 - Event Type Multistate_Value 179 5099_1 RW<br />

Customer Input 3 - Event Control Multistate_Value 180 5100_1 RW<br />

Customer Input 3 - Event Type Multistate_Value 181 5101_1 RW<br />

Customer Input 4 - Event Control Multistate_Value 182 5102_1 RW<br />

Customer Input 4 - Event Type Multistate_Value 183 5103_1 RW<br />

Service Required - Event Control Multistate_Value 184 4727_1 RW<br />

Service Required - Event Type Multistate_Value 185 4728_1 RW<br />

Shutdown - Loss Of Power - Event Control Multistate_Value 186 4715_1 RW<br />

Shutdown - Loss Of Power - Event Type Multistate_Value 187 4716_1 RW<br />

Ext Loss of Flow - Event Control Multistate_Value 188 5082_1 RW<br />

Ext Loss of Flow - Event Type Multistate_Value 189 5083_1 RW<br />

Ext Reheat Lockout - Event Control Multistate_Value 190 5084_1 RW<br />

Ext Reheat Lockout - Event Type Multistate_Value 191 5085_1 RW<br />

Ext Humidifier Lockout - Event Control Multistate_Value 192 5086_1 RW<br />

Ext Humidifier Lockout - Event Type Multistate_Value 193 5087_1 RW<br />

Ext Compressor Lockout - Event Control Multistate_Value 194 5088_1 RW<br />

Ext Compressor Lockout - Event Type Multistate_Value 195 5089_1 RW<br />

Ext Over Temperature - Event Control Multistate_Value 196 5090_1 RW<br />

Ext Over Temperature - Event Type Multistate_Value 197 5091_1 RW<br />

Condenser VFD Issue - Event Control Multistate_Value 198 5092_1 RW<br />

228<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Object<br />

Name Access Notes<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled