184<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - UPS Systems<br />

Table 64 Liebert HiPulse , Liebert SICE 7200 - Input <strong>and</strong> Holding - SMM/SSM (continued)<br />

Controller Multi Module Series - SMM<br />

Liebert Products Liebert HiPulse; Liebert SICE 7200<br />

Available Points<br />

Input Holding # of<br />

Data Description<br />

Register Register Reg. Scale Notes / Units<br />

Battery Test - 40292 1 - Bit 5<br />

Battery Test Failed - 40292 1 - Bit 6<br />

Battery On Load - 40292 1 - Bit 7<br />

Battery End of Discharge - 40292 1 - Bit 8<br />

Boost Time Expired - 40292 1 - Bit 9<br />

DC Overvoltage - 40292 1 - Bit 10<br />

DC Undervoltage - 40293 1 - Bit 0<br />

Battery Fuse Failure - 40293 1 - Bit 1<br />

DC Overvoltage - 40293 1 - Bit 2<br />

Transfer Count Block - 40293 1 - Bit 3<br />

Overload Shutdown - 40293 1 - Bit 4<br />

Overtemperature SD - 40293 1 - Bit 5<br />

Emergency Stop - 40293 1 - Bit 6<br />

Overload Present - 40293 1 - Bit 7<br />

Overload Shutdown TO - 40293 1 - Bit 8<br />

Display Error - 40293 1 - Bit 9<br />

Display Error - 40293 1 - Bit 10<br />

Inverter Over Capacity - 40293 1 - Bit 11<br />

Bypass ECO Mode - 40293 1 - Bit 12<br />

Fan Failure - 40293 1 - Bit 13<br />

If the Scale column has a value for a Data Description, multiply the <strong>Modbus</strong> value by the value in the Scale column.