Table 13 Liebert HPC (Chiller) - Input <strong>and</strong> Holding (continued)<br />

Data Label<br />

Controller Liebert iCOM v4<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Input<br />

Register<br />

Holding<br />

Register<br />

Condensers 3<br />

Condenser Fan Speed<br />

Condenser 4<br />

30416 1 Units : % 2<br />

Condenser Fan Speed<br />

Fluid<br />

30417 1 Units : % 2<br />

Fluid Pressure 30418 1 Scale : x / 10 Units : bar 1, 2<br />

Fluid Cooling Proportional B<strong>and</strong> 30419 40419 1 Scale : x / 10 Units : deg C 1, 2<br />

Fluid Cooling Proportional B<strong>and</strong><br />

Supply (Outlet) Fluid<br />

30420 40420 1 Scale : x / 10 Units : deg F 1, 2<br />

Supply Fluid Temp Set Point 1 30424 40424 1 Scale : x / 10 Units : deg C 1, 2<br />

Supply Fluid Temp Set Point 1 30425 40425 1 Scale : x / 10 Units : deg F 1, 2<br />

Supply Fluid Temp Set Point 2 30426 40426 1 Units : deg C 1, 2<br />

Supply Fluid Temp Set Point 2 30427 40427 1 Units : deg F 1, 2<br />

Supply Fluid Over Temp Alarm Threshold 30430 40430 1 Units : deg C 1, 2<br />

Supply Fluid Over Temp Alarm Threshold 30431 40431 1 Units : deg F 1, 2<br />

Supply Fluid Under Temp Alarm Threshold 30434 40434 1 Units : deg C 1, 2<br />

Supply Fluid Under Temp Alarm Threshold<br />

Pump 1<br />

30435 40435 1 Units : deg F 1, 2<br />

Pump Hours 30450 40450 1 Units : hr 1, 2<br />

Pump Hours Threshold<br />

Pump 2<br />

30451 40451 1 Units : hr 1, 2<br />

Pump Hours 30455 40455 1 Units : hr 1, 2<br />

Pump Hours Threshold<br />

Free Cooling<br />

30456 40456 1 Units : hr 1, 2<br />

Free Cooling External Temperature Delta 30460 40460 1 Units : deg C 1, 2<br />

Free Cooling External Temperature Delta 30461 40461 1 Units : deg F 1, 2<br />

Free Cooling Status 30462 1<br />

0 = off<br />

2 = on<br />

3 = No Support<br />

1, 2<br />

Free Cooling Valve Open Position 30463 1 Units : % 1, 2<br />

Free Cooling Valve Hours 30464 40464 1 Units : hr 1, 2<br />

Free Cooling Valve Hours Threshold 30465 40465 1 Units : hr 1, 2<br />