<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Table 31 Liebert Atlas Air , Liebert Atlas PEC , Liebert LECS 15 - Input <strong>and</strong><br />

Holding - C10 2-step<br />

Controller C10<br />

Liebert Products Liebert Atlas Air; Liebert Atlas PEC; Liebert LECS 15<br />

Available Points<br />

Input Holding # of<br />

Data Description<br />

Status Points (View)<br />

Register Register Reg. Scale Notes / Units<br />

Unit Number - 40001 1 - 1-99<br />

Average Return Air Temp. - 40002 1 10 deg C<br />

Average Return Air Humidity - 40003 1 10 %<br />

Average Supply Air Temp. - 40004 1 10 deg C<br />

Average Supply Air Humidity - 40005 1 10 %<br />

Fan Status - 40007 1 - 1=On / 0=Off<br />

Cool 1 Status - 40008 1 - 1=On / 0=Off<br />

Cool 2 Status - 40009 1 - 1=On / 0=Off<br />

Heat 1 Status - 40010 1 - 1=On / 0=Off<br />

Heat 2 Status - 40011 1 - 1=On / 0=Off<br />

Humidifier Status - 40012 1 - -<br />

De-humidifier Status - 40013 1 - -<br />

Cooling Capacity - 40014 1 - %<br />

Heating Capacity - 40015 1 - %<br />

Temperature Control Status - 40019 1 - 0=Return / 1=Supply<br />

Battery Voltage Level - 40020 1 10 V<br />

Remote Shutdown Status - 40021 1 - 1=Enabled / 0=Disabled<br />

Temperature Control Select - 40024 1 -<br />

0=Return / 1=Supply<br />

2=Remote / 3=Auto<br />

Alarm Points -<br />

Communications - 40289 1 - Bit 0<br />

Faulty Sensor - 40289 1 - Bit 1<br />

High Temperature - 40289 1 - Bit 2<br />

Low Temperature - 40289 1 - Bit 3<br />

High Humidity - 40289 1 - Bit 4<br />

Low Humidity - 40289 1 - Bit 5<br />

Loss of Airflow - 40289 1 - Bit 6<br />

Water Under Floor - 40289 1 - Bit 7<br />

Cool 1 Low Pressure Alarm - 40289 1 - Bit 8<br />

Cool 2 Low Pressure Alarm - 40289 1 - Bit 9<br />

Cool 1 High Pressure Alarm - 40289 1 - Bit 10<br />

Cool 2 High Pressure Alarm - 40290 1 - Bit 0<br />

Cool Service - 40290 1 - Bit 1<br />

Humidifier Service - 40290 1 - Bit 2<br />

Filter Service - 40290 1 - Bit 3<br />

Humidity Low Level - 40290 1 - Bit 4<br />

Battery Level Low - 40290 1 - Bit 5<br />

Loss of Power - 40290 1 - Bit 6<br />

Local Alarm 1 - 40290 1 - Bit 7<br />

Local Alarm 2 - 40290 1 - Bit 8<br />