<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Table 69 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert<br />

DS, Liebert HPM, Liebert PeX - Binary Data (continued)<br />

Controller Liebert iCOM v4<br />

Data Description Object Type Instance<br />

Object<br />

Name Access Notes<br />

Free Cooling<br />

Free Cooling Valve Hours Exceeded Binary_Value 117 5306_1 RD -<br />

Ext Free Cooling Lockout Binary_Value 118 5361_1 RD -<br />

Free Cooling Temp Sensor Issue<br />

Reheat<br />

Binary_Value 119 5362_1 RD -<br />

Hot Water / Hot Gas Valve Hours Exceeded Binary_Value 130 5365_1 RD -<br />

Reheater Over Temperature Binary_Value 131 5068_1 RD -<br />

Ext Reheat Lockout<br />

Reheat - Electric Reheater 1<br />

Binary_Value 132 5070_1 RD -<br />

Electric Reheater Hours Exceeded<br />

Reheat - Electric Reheater 2<br />

Binary_Value 143 5368_1_1 RD -<br />

Electric Reheater Hours Exceeded<br />

Reheat - Electric Reheater 3<br />

Binary_Value 154 5368_1_2 RD -<br />

Electric Reheater Hours Exceeded<br />

Humidifier<br />

Binary_Value 165 5368_1_3 RD -<br />

Humidifier Hours Exceeded Binary_Value 176 5037_1 RD -<br />

Ext Humidifier Lockout Binary_Value 177 5044_1 RD -<br />

Humidifier Control Board Not Detected Binary_Value 178 5045_1 RD -<br />

Humidifier Cylinder Worn Binary_Value 179 5042_1 RD -<br />

Humidifier Issue Binary_Value 180 5043_1 RD -<br />

Humidifier Low Water Binary_Value 181 5041_1 RD -<br />

Humidifier Over Current Binary_Value 182 5040_1 RD -<br />

Humidifier Under Current<br />

Dehumidifier<br />

Binary_Value 183 5039_1 RD -<br />

Dehumidifier Hours Exceeded<br />

Fan<br />

Binary_Value 194 5038_1 RD -<br />

Fan Hours Exceeded Binary_Value 205 5054_1 RD -<br />

Main Fan Overload Binary_Value 206 5376_1 RD -<br />

Fan Issue<br />

Condensers<br />

Binary_Value 207 4729_1 RD -<br />

Condenser TVSS Issue Binary_Value 218 5073_1 RD -<br />

Condenser VFD Issue Binary_Value 219 5072_1 RD -<br />

Ext Condenser Pump High Water<br />

Condensers - Condenser 1<br />

Binary_Value 220 5106_1 RD -<br />

Condenser Issue<br />

Condensers - Condenser 2<br />

Binary_Value 231 5377_1_1 RD -<br />

Condenser Issue<br />

System Events<br />

Binary_Value 242 5377_1_2 RD -<br />

Customer Input 1 Binary_Value 253 4270_1 RD -<br />

Customer Input 2 Binary_Value 254 4271_1 RD -<br />

Customer Input 3 Binary_Value 255 4272_1 RD -<br />

Customer Input 4 Binary_Value 256 4273_1 RD -<br />

Ext Loss of Air Blower Binary_Value 257 5415_1 RD -<br />

Ext Loss of Flow Binary_Value 258 5105_1 RD -<br />

Ext St<strong>and</strong>by Glycol Pump On Binary_Value 259 5107_1 RD -<br />

BMS Communications Timeout Binary_Value 260 5115_1 RD -