Table 16 Liebert XDC - Input <strong>and</strong> Holding (continued)<br />

Data Description<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Visual ID Control 30476 40476 1<br />

0 = disabled<br />

1 = enabled<br />

Cooling Capacity 30477 1 Units : %<br />

Cooling Capacity 30478 1 Units : kW<br />

Ext System Condensation Detected - Event<br />

Control<br />

Ext System Condensation Detected - Event<br />

Type<br />

30479 40479 1<br />

30480 40480 1<br />

Ext Fan Issue - Event Control 30481 40481 1<br />

Ext Fan Issue - Event Type 30482 40482 1<br />

Sensor Issue - Event Control 30483 40483 1<br />

Sensor Issue - Event Type 30484 40484 1<br />

Ext Remote Shutdown - Event Control 30<strong>485</strong> 40<strong>485</strong> 1<br />

58<br />

0 = disabled<br />

1 = enabled<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

0 = disabled<br />

1 = enabled<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

0 = disabled<br />

1 = enabled<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

0 = disabled<br />

1 = enabled<br />

Ext Remote Shutdown - Event Type 30486 40486 1<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

Hot Aisle Over Temp Threshold 30487 40487 1 Units : deg C<br />

Hot Aisle Over Temp Threshold 30488 40488 1 Units : deg F<br />

Hot Aisle Under Temp Threshold 30489 40489 1 Units : deg C<br />

Hot Aisle Under Temp Threshold 30490 40490 1 Units : deg F<br />

Cold Aisle Over Temp Threshold 30491 40491 1 Units : deg C<br />

Cold Aisle Over Temp Threshold 30492 40492 1 Units : deg F<br />

Cold Aisle Under Temp Threshold 30493 40493 1 Units : deg C<br />

Cold Aisle Under Temp Threshold<br />

XD System 20<br />

30494 40494 1 Units : deg F<br />

Communication Status 30976 1<br />

Fan On/Off Control 30977 40977 1<br />

Primary Fan Group State 30978 1<br />

Fan Button Control 30979 40979 1<br />

0 = Connected<br />

1 = Not Connected<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

2 = economy<br />

0 = enabled<br />

1 = disabled<br />

Visual ID Control 30980 40980 1<br />

0 = disabled<br />

1 = enabled<br />

Cooling Capacity 30981 1 Units : %<br />

Cooling Capacity 30982 1 Units : kW<br />

Ext System Condensation Detected - Event<br />

Control<br />

Ext System Condensation Detected - Event<br />

Type<br />

Controller Liebert iCOM v4<br />

Input<br />

Register<br />

Holding<br />

Register<br />

30983 40983 1<br />

30984 40984 1<br />

# of<br />

Reg. Scale Notes / Units<br />

0 = disabled<br />

1 = enabled<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm