Table 15 Liebert XDC - Status <strong>and</strong> Coil<br />

Controller Liebert iCOM v4<br />

Data Description Status Coil<br />

Number<br />

of Bits Notes<br />

Pumps<br />

Pump 1 Loss of Flow 10001 1 Active on Alarm<br />

Pump 2 Loss of Flow 10002 1 Active on Alarm<br />

Pump Short Cycle<br />

System Events<br />

10016 1 Active on Alarm<br />

Fan Issue 10003 1 Active on Alarm<br />

System Condensation Detected 10004 1 Active on Alarm<br />

Customer Input 1 10005 1 Active on Alarm<br />

Shutdown - Loss Of Power 10027 1 Active on Alarm<br />

Smoke Detected 10028 1 Active on Alarm<br />

Water Under Floor 10029 1 Active on Alarm<br />

Service Required 10030 1 Active on Alarm<br />

Unit Communication Lost 10272 1 Active on Alarm<br />

RAM Battery Issue 10273 1 Active on Alarm<br />

Master Unit Communication Lost 10274 1 Active on Alarm<br />

Remote Shutdown 10275 1 Active on Alarm<br />

Unit Code Missing<br />

Refridgerant<br />

10276 1 Active on Alarm<br />

Supply Refrigerant Over Temp 10006 1 Active on Alarm<br />

Supply Refrigerant Under Temp 10007 1 Active on Alarm<br />

Supply Refrigerant Temp Sensor Issue<br />

External Air<br />

10008 1 Active on Alarm<br />

Ext Air Sensor A Over Temperature 10009 1 Active on Alarm<br />

Ext Air Sensor A Under Temperature 10010 1 Active on Alarm<br />

Ext Air Sensor A Issue 10011 1 Active on Alarm<br />

Ext Air Sensor B Over Temperature 10012 1 Active on Alarm<br />

Ext Air Sensor B Under Temperature 10013 1 Active on Alarm<br />

Ext Air Sensor B Issue 10014 1 Active on Alarm<br />

Ext Dew Point Over Temperature<br />

Compressor<br />

10015 1 Active on Alarm<br />

Compressor 1A High Head Pressure 10017 1 Active on Alarm<br />

Compressor 1B High Head Pressure 10018 1 Active on Alarm<br />

Compressor 2A High Head Pressure 10019 1 Active on Alarm<br />

Compressor 2B High Head Pressure 10020 1 Active on Alarm<br />

Compressor 1A Short Cycle 10021 1 Active on Alarm<br />

Compressor 1B Short Cycle 10022 1 Active on Alarm<br />

Compressor 2A Short Cycle 10023 1 Active on Alarm<br />

Compressor 2B Short Cycle 10024 1 Active on Alarm<br />

Circuit 1 Low Suction Pressure 10025 1 Active on Alarm<br />

Circuit 2 Low Suction Pressure<br />

Pump Hours 1<br />

10026 1 Active on Alarm<br />

Pump Hours Exceeded<br />

Pump Hours 2<br />

10040 1 Active on Alarm<br />

Pump Hours Exceeded 10046 1 Active on Alarm<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />