Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Table 15 Liebert XDC - Status <strong>and</strong> Coil<br />
Controller Liebert iCOM v4<br />
Data Description Status Coil<br />
Number<br />
of Bits Notes<br />
Pumps<br />
Pump 1 Loss of Flow 10001 1 Active on Alarm<br />
Pump 2 Loss of Flow 10002 1 Active on Alarm<br />
Pump Short Cycle<br />
System Events<br />
10016 1 Active on Alarm<br />
Fan Issue 10003 1 Active on Alarm<br />
System Condensation Detected 10004 1 Active on Alarm<br />
Customer Input 1 10005 1 Active on Alarm<br />
Shutdown - Loss Of Power 10027 1 Active on Alarm<br />
Smoke Detected 10028 1 Active on Alarm<br />
Water Under Floor 10029 1 Active on Alarm<br />
Service Required 10030 1 Active on Alarm<br />
Unit Communication Lost 10272 1 Active on Alarm<br />
RAM Battery Issue 10273 1 Active on Alarm<br />
Master Unit Communication Lost 10274 1 Active on Alarm<br />
Remote Shutdown 10275 1 Active on Alarm<br />
Unit Code Missing<br />
Refridgerant<br />
10276 1 Active on Alarm<br />
Supply Refrigerant Over Temp 10006 1 Active on Alarm<br />
Supply Refrigerant Under Temp 10007 1 Active on Alarm<br />
Supply Refrigerant Temp Sensor Issue<br />
External Air<br />
10008 1 Active on Alarm<br />
Ext Air Sensor A Over Temperature 10009 1 Active on Alarm<br />
Ext Air Sensor A Under Temperature 10010 1 Active on Alarm<br />
Ext Air Sensor A Issue 10011 1 Active on Alarm<br />
Ext Air Sensor B Over Temperature 10012 1 Active on Alarm<br />
Ext Air Sensor B Under Temperature 10013 1 Active on Alarm<br />
Ext Air Sensor B Issue 10014 1 Active on Alarm<br />
Ext Dew Point Over Temperature<br />
Compressor<br />
10015 1 Active on Alarm<br />
Compressor 1A High Head Pressure 10017 1 Active on Alarm<br />
Compressor 1B High Head Pressure 10018 1 Active on Alarm<br />
Compressor 2A High Head Pressure 10019 1 Active on Alarm<br />
Compressor 2B High Head Pressure 10020 1 Active on Alarm<br />
Compressor 1A Short Cycle 10021 1 Active on Alarm<br />
Compressor 1B Short Cycle 10022 1 Active on Alarm<br />
Compressor 2A Short Cycle 10023 1 Active on Alarm<br />
Compressor 2B Short Cycle 10024 1 Active on Alarm<br />
Circuit 1 Low Suction Pressure 10025 1 Active on Alarm<br />
Circuit 2 Low Suction Pressure<br />
Pump Hours 1<br />
10026 1 Active on Alarm<br />
Pump Hours Exceeded<br />
Pump Hours 2<br />
10040 1 Active on Alarm<br />
Pump Hours Exceeded 10046 1 Active on Alarm<br />
<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />
53