<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Power Distribution <strong>and</strong> Power Conditioning Products<br />

Table 35 Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC Liebert RDC, Liebert RX - Status <strong>and</strong> Coil<br />

Controller v4<br />

Liebert Products Liebert EXC, Libert FDC, Liebert FPC, Liebert PPC Liebert RDC, Liebert RX<br />

Available Points<br />

Number<br />

Data Description<br />

Input Power 1<br />

Status Coil of Bits Scale Notes / Units<br />

Phase Loss 10001 - 1 - Active on Alarm<br />

Phase Rotation Error<br />

Input Power 2<br />

10002 - 1 - Active on Alarm<br />

Phase Loss 10013 - 1 - Active on Alarm<br />

Phase Rotation Error<br />

Output Power 1<br />

10014 - 1 - Active on Alarm<br />

Output Overvoltage 10025 - 1 - Active on Alarm<br />

Output Undervoltage 10026 - 1 - Active on Alarm<br />

Output Overcurrent 10027 - 1 - Active on Alarm<br />

Neutral Overcurrent 10028 - 1 - Active on Alarm<br />

Ground Overcurrent 10029 - 1 - Active on Alarm<br />

Output Voltage THD 10030 - 1 - Active on Alarm<br />

Frequency Deviation 10031 - 1 - Active on Alarm<br />

Transformer Overtemperature Power Off 10032 - 1 - Active on Alarm<br />

Transformer Overtemperature 10033 - 1 - Active on Alarm<br />

Transformer Temperature Sensor Fail<br />

Output Power 2<br />

10034 - 1 - Active on Alarm<br />

Output Overvoltage 10045 - 1 - Active on Alarm<br />

Output Undervoltage 10046 - 1 - Active on Alarm<br />

Output Overcurrent 10047 - 1 - Active on Alarm<br />

Neutral Overcurrent 10048 - 1 - Active on Alarm<br />

Ground Overcurrent 10049 - 1 - Active on Alarm<br />

Output Voltage THD 10050 - 1 - Active on Alarm<br />

Frequency Deviation 10051 - 1 - Active on Alarm<br />

Transformer Overtemperature Power Off 10052 - 1 - Active on Alarm<br />

Transformer Overtemperature 10053 - 1 - Active on Alarm<br />

Transformer Temperature Sensor Fail<br />

Panel 1<br />

10054 - 1 - Active on Alarm<br />

Panel Summary Alarm 10065 - 1 - Active on Alarm<br />

Panel Overvoltage 10066 - 1 - Active on Alarm<br />

Panel Undervoltage 10067 - 1 - Active on Alarm<br />

Panel Phase Overcurrent 10068 - 1 - Active on Alarm<br />

Panel Phase Overcurrent 10069 - 1 - Active on Warning<br />

Panel Neutral Overcurrent 10070 - 1 - Active on Alarm<br />

Panel Ground Overcurrent<br />

Panel 2<br />

10071 - 1 - Active on Alarm<br />

Panel Summary Alarm 10082 - 1 - Active on Alarm<br />

Panel Overvoltage 10083 - 1 - Active on Alarm<br />

Panel Undervoltage 10084 - 1 - Active on Alarm<br />

Panel Phase Overcurrent 10085 - 1 - Active on Alarm<br />

Panel Phase Overcurrent 10086 - 1 - Active on Warning<br />

Panel Neutral Overcurrent 10087 - 1 - Active on Alarm<br />

Panel Ground Overcurrent 10088 - 1 - Active on Alarm<br />

113