<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Table 32 Liebert Atlas Air, Liebert Atlas PEC, Liebert CEMS 100 - Input <strong>and</strong><br />

Holding - C100 4-step (continued)<br />

Controller CEMS 100<br />

Liebert Products Liebert Atlas Air; Liebert Atlas PEC; Liebert CEMS 100<br />

Available Points<br />

Input Holding # of<br />

Data Description Register Register Reg. Scale Notes / Units<br />

Cooling Capacity - 40014 1 - %<br />

Heating Capacity - 40015 1 - %<br />

Temperature Control Status - 40019 1 - 0=Return / 1=Supply<br />

Battery Voltage Level - 40020 1 100 V<br />

Remote Shutdown Status - 40021 1 - 1=Enabled / 0=Disabled<br />

Temperature Control Select - 40024 1 -<br />

0=Return / 1=Supply<br />

2=Remote / 3=Auto<br />

Alarm Points -<br />

Communications - 40289 1 - Bit 0<br />

Faulty Sensor - 40289 1 - Bit 1<br />

High Temperature - 40289 1 - Bit 2<br />

Low Temperature - 40289 1 - Bit 3<br />

High Humidity - 40289 1 - Bit 4<br />

Low Humidity - 40289 1 - Bit 5<br />

Loss of Airflow - 40289 1 - Bit 6<br />

Water Under Floor - 40289 1 - Bit 7<br />

Cool 1 Low Pressure Alarm - 40289 1 - Bit 8<br />

Cool 2 Low Pressure Alarm - 40289 1 - Bit 9<br />

Cool 1 High Pressure Alarm - 40289 1 - Bit 10<br />

Cool 2 High Pressure Alarm - 40290 1 - Bit 0<br />

Cool Service - 40290 1 - Bit 1<br />

Humidifier Service - 40290 1 - Bit 2<br />

Filter Service - 40290 1 - Bit 3<br />

Humidity Low Level - 40290 1 - Bit 4<br />

Battery Level Low - 40290 1 - Bit 5<br />

Loss of Power - 40290 1 - Bit 6<br />

Local Alarm 1 - 40290 1 - Bit 7<br />

Local Alarm 2 - 40290 1 - Bit 8<br />

Cool 3 Low Pressure - 40290 1 - Bit 9<br />

Cool 4 Low Pressure - 40290 1 - Bit 10<br />

Cool 3 High Pressure - 40290 1 - Bit 11<br />

Cool 4 High Pressure - 40290 1 - Bit 12<br />

Air Flow 2 Loss<br />

Setpoints (View)<br />

- 40290 1 - Bit 13<br />

Return Air Temperature - 40016 1 10 deg C (R/W)<br />

Return Air Humidity - 40017 1 10 deg C (R/W)<br />

Supply Air Temperature - 40018 1 10 deg C (R/W)<br />

High Temp Alarm - 40025 1 10 deg C (R/W)<br />

Low Temp Alarm - 40026 1 10 deg C (R/W)<br />