206<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Table 71 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert<br />

DS, Liebert HPM, Liebert PeX - Multistate Data (continued)<br />

Controller Liebert iCOM v4<br />

Object<br />

Data Description<br />

Compressors - Compressor 1<br />

Object Type Instance Name Access Notes<br />

Compressor State Multistate_Value 45 5264_1_1 RD 1 = Off / 2 = On<br />

Compressor Capacity Control State<br />

Compressors - Compressor 2<br />

Multistate_Value 46 5265_1_1 RD 1 = Off / 2 = On<br />

Compressor State Multistate_Value 57 5264_1_2 RD 1 = Off / 2 = On<br />

Compressor Capacity Control State<br />

Free Cooling<br />

Multistate_Value 58 5265_1_2 RD 1 = Off / 2 = On<br />

Free Cooling Status Multistate_Value 69 5302_1 RD<br />

1 = Off / 2 = On<br />

3 = No Support<br />

1 = Disabled<br />

Free Cooling Internal Control Mode Multistate_Value 70 5357_1 RW 2 = Contact<br />

3 = Value<br />

Minimum Chilled Water Temp Set Point Enable<br />

Fan<br />

Multistate_Value 71 5359_1 RW<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Auto<br />

Fan Control Mode<br />

System Info<br />

Multistate_Value 82 5373_1 RW<br />

2 = Manual<br />

3 = Economy<br />

4 = Delta<br />

1 = Normal Operation<br />

2 = StartUp<br />

System Status Multistate_Value 93 4123_1 RD 3 = Normal with Warning<br />

4 = Normal with Alarm<br />

5 = Abnormal Operation<br />

System Operating State Multistate_Value 94 4706_1 RD<br />

1 = Off / 2 = On<br />

3 = St<strong>and</strong>by<br />

System Control Mode Multistate_Value 95 4707_1 RD<br />

1 = Internal (Auto)<br />

2 = External (Manual)<br />

1 = Reason Unknown<br />

2 = Network Display<br />

3 = Alarm<br />

System Operating State Reason<br />

System Operations<br />

Multistate_Value 96 5074_1 RD 4 = Schedule<br />

5 = Remote System<br />

6 = External Input<br />

7 = Local Display<br />

Fan State Multistate_Value 107 5381_1 RD 1 = Off / 2 = On<br />

Cooling State Multistate_Value 108 5382_1 RD 1 = Off / 2 = On<br />

Free Cooling State Multistate_Value 109 5383_1 RD 1 = Off / 2 = On<br />

Maintenance Tracking State Multistate_Value 110 5384_1 RD 1 = Off / 2 = On<br />

Hot Water / Hot Gas State Multistate_Value 111 5385_1 RD 1 = Off / 2 = On<br />

Electric Reheat State Multistate_Value 112 5386_1 RD 1 = Off / 2 = On<br />

Dehumidifier State Multistate_Value 113 5387_1 RD 1 = Off / 2 = On<br />

Humidifier State Multistate_Value 114 5388_1 RD 1 = Off / 2 = On<br />

System On/Off Control<br />

System Event Configuration<br />

Multistate_Value 115 5143_1 RW 1 = Off / 2 = On