209<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Table 71 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert<br />

DS, Liebert HPM, Liebert PeX - Multistate Data (continued)<br />

Clogged Air Filter - Event Control Multistate_Value 166 5135_1 RW<br />

Clogged Air Filter - Event Type Multistate_Value 167 5136_1 RW<br />

Ext Loss of Air Blower - Event Control Multistate_Value 168 5393_1 RW<br />

Ext Loss of Air Blower - Event Type Multistate_Value 169 5394_1 RW<br />

System Event Configuration - Compressor 1<br />

Compressor High Head Pressure - Event<br />

Control<br />

Multistate_Value 180 5316_1_1 RW<br />

Compressor High Head Pressure - Event Type Multistate_Value 181 5317_1_1 RW<br />

Compressor Low Suction Pressure - Event<br />

Control<br />

Multistate_Value 182 5318_1_1 RW<br />

Compressor Low Suction Pressure - Event Type Multistate_Value 183 5319_1_1 RW<br />

Compressor Pump Down Issue - Event Control Multistate_Value 184 5395_1_1 RW<br />

Compressor Pump Down Issue - Event Type Multistate_Value 185 5396_1_1 RW<br />

Compressor Short Cycle - Event Control Multistate_Value 186 5397_1_1 RW<br />

Compressor Short Cycle - Event Type Multistate_Value 187 5398_1_1 RW<br />

Compressor Thermal Overload - Event Control Multistate_Value 188 5320_1_1 RW<br />

Compressor Thermal Overload - Event Type Multistate_Value 189 5321_1_1 RW<br />

Dig Scroll Comp Discharge Over Temp - Event<br />

Ctrl<br />

Dig Scroll Comp Discharge Over Temp - Event<br />

Type<br />

System Event Configuration - Compressor 2<br />

Compressor High Head Pressure - Event<br />

Control<br />

Multistate_Value 190 5399_1_1 RW<br />

Multistate_Value 191 5400_1_1 RW<br />

Multistate_Value 202 5316_1_2 RW<br />

Compressor High Head Pressure - Event Type Multistate_Value 203 5317_1_2 RW<br />

Compressor Low Suction Pressure - Event<br />

Control<br />

Controller Liebert iCOM v4<br />

Data Description Object Type Instance<br />

Multistate_Value 204 5318_1_2 RW<br />

Object<br />

Name Access Notes<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled