Table 19 Liebert XDP - Input <strong>and</strong> Holding (continued)<br />

Data Label<br />

Ext System Condensation Detected - Event<br />

Type<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

30452 40452 1<br />

Ext Fan Issue - Event Control 30453 40453 1<br />

Ext Fan Issue - Event Type 30454 40454 1<br />

Sensor Issue - Event Control 30455 40455 1<br />

Sensor Issue - Event Type 30456 40456 1<br />

Ext Remote Shutdown - Event Control 30457 40457 1<br />

74<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

0 = disabled<br />

1 = enabled<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

0 = disabled<br />

1 = enabled<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

0 = disabled<br />

1 = enabled<br />

Ext Remote Shutdown - Event Type 30458 40458 1<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

Hot Aisle Over Temp Threshold 30459 40459 1 Units : deg C<br />

Hot Aisle Over Temp Threshold 30460 40460 1 Units : deg F<br />

Hot Aisle Under Temp Threshold 30461 40461 1 Units : deg C<br />

Hot Aisle Under Temp Threshold 30462 40462 1 Units : deg F<br />

Cold Aisle Over Temp Threshold 30463 40463 1 Units : deg C<br />

Cold Aisle Over Temp Threshold 30464 40464 1 Units : deg F<br />

Cold Aisle Under Temp Threshold 30465 40465 1 Units : deg C<br />

Cold Aisle Under Temp Threshold<br />

XD System 2<br />

30466 40466 1 Units : deg F<br />

Communication Status 30472 1<br />

Fan On/Off Control 30473 40473 1<br />

Primary Fan Group State 30474 1<br />

Fan Button Control 30475 40475 1<br />

0 = Connected<br />

1 = Not Connected<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

2 = economy<br />

0 = enabled<br />

1 = disabled<br />

Visual ID Control 30476 40476 1<br />

0 = disabled<br />

1 = enabled<br />

Cooling Capacity 30477 1 Units : %<br />

Cooling Capacity 30478 1 Units : kW<br />

Ext System Condensation Detected - Event<br />

Control<br />

Ext System Condensation Detected - Event<br />

Type<br />

Input<br />

Register<br />

30479 40479 1<br />

30480 40480 1<br />

Ext Fan Issue - Event Control 30481 40481 1<br />

Ext Fan Issue - Event Type 30482 40482 1<br />

Holding<br />

Register # of Reg Scale Notes/Units<br />

0 = disabled<br />

1 = enabled<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm<br />

0 = disabled<br />

1 = enabled<br />

0 = Message<br />

1 = Warning<br />

2 = Alarm