Table 19 Liebert XDP - Input <strong>and</strong> Holding (continued)<br />

Data Label<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

External Air<br />

Ext Air Sensor A Temperature 30393 1 Scale : x / 10 Units : deg C<br />

Ext Air Sensor A Temperature 30394 1 Scale : x / 10 Units : deg F<br />

Ext Air Sensor A Humidity 30395 1 Scale : x / 10 Units : % RH<br />

Ext Air Sensor A Dew Point Temp 30396 1 Scale : x / 10 Units : deg C<br />

Ext Air Sensor A Dew Point Temp 30397 1 Scale : x / 10 Units : deg F<br />

Ext Air Sensor B Temperature 30398 1 Scale : x / 10 Units : deg C<br />

Ext Air Sensor B Temperature 30399 1 Scale : x / 10 Units : deg F<br />

Ext Air Sensor B Humidity 30400 1 Scale : x / 10 Units : % RH<br />

Ext Air Sensor B Dew Point Temp 30401 1 Scale : x / 10 Units : deg C<br />

Ext Air Sensor B Dew Point Temp 30402 1 Scale : x / 10 Units : deg F<br />

Minimum Room Temperature Set Point 30403 40403 1 Scale : x / 10 Units : deg C<br />

Minimum Room Temperature Set Point 30404 40404 1 Scale : x / 10 Units : deg F<br />

Ext Air Over Temp Threshold 30405 40405 1 Scale : x / 10 Units : deg C<br />

Ext Air Over Temp Threshold 30406 40406 1 Scale : x / 10 Units : deg F<br />

Ext Air Under Temp Threshold 30407 40407 1 Scale : x / 10 Units : deg C<br />

Ext Air Under Temp Threshold 30408 40408 1 Scale : x / 10 Units : deg F<br />

Ext Dew Point Over Temp Threshold 30409 40409 1 Scale : x / 10 Units : deg C<br />

Ext Dew Point Over Temp Threshold 30410 40410 1 Scale : x / 10 Units : deg F<br />

Dew Point Temperature 30415 1 Scale : x / 10 Units : deg C<br />

Dew Point Temperature<br />

Time<br />

30416 1 Scale : x / 10 Units : deg F<br />

System Date <strong>and</strong> Time<br />

Pump Hours 1<br />

39998 49998 2 Secs since Epoch(UTC)<br />

Pump Hours 30430 40430 1 Units : hr<br />

Pump Hours Threshold<br />

Pump Hours 2<br />

30431 40431 1 Units : hr<br />

Pump Hours 30437 40437 1 Units : hr<br />

Pump Hours Threshold<br />

XD System 1<br />

30438 40438 1 Units : hr<br />

Communication Status 30444 1<br />

Fan On/Off Control 30445 40445 1<br />

Primary Fan Group State 30446 1<br />

Fan Button Control 30447 40447 1<br />

73<br />

0 = Connected<br />

1 = Not Connected<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

2 = economy<br />

0 = enabled<br />

1 = disabled<br />

Visual ID Control 30448 40448 1<br />

0 = disabled<br />

1 = enabled<br />

Cooling Capacity 30449 1 Units : %<br />

Cooling Capacity 30450 1 Units : kW<br />

Ext System Condensation Detected - Event<br />

Control<br />

Input<br />

Register<br />

Holding<br />

Register # of Reg Scale Notes/Units<br />

30451 40451 1<br />

0 = disabled<br />

1 = enabled