Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert<br />

DS, Liebert HPM, Liebert PeX - Glossary<br />

Controller Liebert iCOM v4<br />

Data Description Description<br />

Actual Air Temperature Set Point<br />

The actual set point being used for air temperature control. This value may differ from<br />

[Air Temperature Set Point] if compensation is applied by the control.<br />

Actual Humidity Set Point<br />

The actual set point being used for humidity control. This value may differ from<br />

[Humidity Set Point] if compensation is applied by the control.<br />

Humidity value being used for control. This value may differ from the actual measured<br />

Adjusted Humidity<br />

[Return Humidity] based on several factors which may include, but are not limited to,<br />

selection of humidity control sensor <strong>and</strong> humidity control type.<br />

Air Economizer Availability<br />

Indicates if the outside air conditions are appropriate for cooling with the air<br />

economizer or glycol freecooling.<br />

Air Economizer Control Source Source of control of the air economizer.<br />

Air Economizer Emergency<br />

Override<br />

Indoor room temperature has exceeded its upper threshold <strong>and</strong> the outdoor air damper<br />

has been opened for emergency cooling.<br />

Air Economizer Reduced Airflow Air economizer filter is dirty <strong>and</strong> needs to be cleaned or replaced.<br />

Air Temperature Control Integration<br />

Time<br />

Time value used when system is under integral air temperature control.<br />

Air Temperature Control Sensor<br />

Sensor from which air temperature measurements will be used for cooling <strong>and</strong> heating<br />

control.<br />

Air Temperature Control Type Type of algorithm used to control the system's output air temperature.<br />

Value that is divided evenly to form a temperature range above <strong>and</strong> below [Air<br />

Air Temperature Dead B<strong>and</strong> Temperature Set Point]. If measured air temperature is within this range, no heating or<br />

cooling will occur.<br />

Air Temperature Proportional B<strong>and</strong><br />

Value that is divided evenly to form proportional temperature control b<strong>and</strong>s above <strong>and</strong><br />

below [Air Temperature Set Point].<br />

Air Temperature Set Point<br />

Desired air temperature. This set point is dependent upon which sensor is selected for<br />

control.<br />

Ambient Air Sensor Issue Ambient air sensor is disconnected or the signal is out of range.<br />

Analog Input Reading Generic analog input reading (unitless).<br />

Auto Restart Delay<br />

If power is lost, the control will delay this amount of time after power is restored before<br />

restarting the unit.<br />

BMS Communications Timeout<br />

Building Management System (or external monitoring system) has not communicated<br />

with the system within the expected timeframe.<br />

BMS Timeout Period<br />

Timeframe within which the Building Management System (or external monitoring<br />

system) must communicate with the system to avoid a timeout.<br />

Calculated Next Maintenance Calculated month of the next scheduled maintenance. Used in conjunction with<br />

Month<br />

[Calculated Next Maintenance Year].<br />

Calculated Next Maintenance Year<br />

Calculated year of the next scheduled maintenance. Used in conjunction with<br />

[Calculated Next Maintenance Month].<br />

Chilled Water Control Valve Failure<br />

Chilled water valve out of position. Chilled water control valve position does not match<br />

expected value.<br />

Operating hours for chilled water valve since last reset of this value. If operating hours<br />

Chilled Water Valve Hours<br />

exceeds 32,000, this client will continue to display 32,000, but the iCOM display will<br />

show the actual value.<br />

Enable/disable the activation of the [Clogged Air Filter] event. If set to 'disabled', the<br />

Clogged Air Filter - Event Control event will not be annunciated. This implies that the event will not be placed in any<br />

active event list or in any event history list.<br />

Clogged Air Filter - Event Type The event type for the [Clogged Air Filter] event.<br />

Clogged Air Filter Air filter is dirty <strong>and</strong> needs to be (cleaned or) replaced.<br />

Compressor Capacity Control State<br />

Compressor capacity control state. When 'ON', the cooling capacity of the compressor<br />

has been reduced.<br />

Compressor Capacity Reduced Compressor capacity has been reduced.<br />

Compressor High Head Pressure -<br />

Event Control<br />

Enable/disable the activation of the [Compressor High Head Pressure] event. If set to<br />

'disabled', the event will not be annunciated. This implies that the event will not be<br />

placed in any active event list or in any event history list.<br />

Compressor High Head Pressure -<br />

Event Type<br />

The event type for the [Compressor High Head Pressure] event.<br />

22