displacement influence lines and stress influence line. <strong>The</strong> measured displacement range at GPS instrument<br />

point: GP04 is 115 mm (or 1.4 mm per ton), and the corresponding measured stress range at strain instrument<br />

point: SW60X is 16 MPa (or 0.195 MPa per ton).<br />

3.4.4 Global Dynamic Features Monitoring (Figures 38-39)<br />

Four hours of time-series acceleration data obtained from the two nos. of accelerometers installed inside the<br />

steel deck-section at mid main span are used. <strong>The</strong> time duration for one data frame used is 30 minutes and the<br />

total number of data points per data frame is 180,000 which are computed on a sampling rate of 100 Hz. <strong>The</strong><br />

frequency resolution for extraction is therefore 0.000556 Hz. <strong>The</strong> total number of data frames considered in<br />

average is fifteen and the corresponding wind speed and air temperature references are respective 2.05 m/s<br />

(10-miniute mean) and 16.4~17.5°C. <strong>The</strong> result of vertical flexural deck frequencies (the first 20 nos.) extracted<br />

from the power spectrum is shown in Figures 38. Of these 20 measured frequencies, 16 of them are<br />

corresponding to the analyzed results. <strong>The</strong> comparison between the measured results and analyzed results (by<br />

normal mode analysis of a 3D space frame finite element model – built and analyzed by ANSYS/Multiphysics<br />

[Ref. 38]) is shown in Figure 39. <strong>The</strong> comparison shows good correlation between measured and analyzed<br />

results, and the model is reliable and accuracy for the analysis of highway load-effects.<br />

3.4.5 Stay Forces Monitoring (Figures 40-41)<br />

<strong>The</strong> example of stay forces monitoring is refers to the ambient vibration works which was requested by the<br />

Engineer for checking the as-built stay forces with their computed stay forces under their reference (completion)<br />

conditions [Ref. 36]. A total of 224 stay cables were measured in the seven nights during the period of 4-12<br />

November 2009. Figure 40 illustrates the installation of accelerometer on stay cable and corresponding<br />

procedures of data processing and analysis. Figure 41 illustrates the results of stay forces in the main span of<br />

East Tower – North side obtained from the Engineer, the Contractor and Highways Department.<br />

3.4.6 Displacements Monitoring (Figures 42-43)<br />

<strong>The</strong> displacements monitoring refers to the input of the GPS data into the pre-built finite element bridge model<br />

and re-generate the deflected bridge geometry profile/profiles and stress contours with stresses output at<br />

key/instrumented structural sections/locations. Figure 42 illustrates the derived displacement profile (with<br />

colour contours) of Stonecutters Bridge, and Figure 43 shows the corresponding derived stress in deck trough<br />

sections.<br />

3.4.7 Fatigue Damages Monitoring (Figures 44-45)<br />

<strong>The</strong> example of fatigue damages monitoring is based on the results of dynamic strain gauges installed in the<br />

deck trough section at bottom of north longitudinal box at mid main span. Figure 44 shows the stress demand<br />

ratio plot, which is used to detect whether the measured stress range at deck trough section exceeding the<br />

maximum allowable stress range of 35 MPa (Class F2). If the measured stress range exceeds the maximum<br />

allowable limit, then micro-cracks might be occurred and the Palmgren-Miner rule cannot be applied in fatigue<br />

assessment. As Figure 44 shows that the maximum measured stress range at the deck trough section considered<br />

is 9.99 MPa, which is much less than the allowable stress range of 35 MPa (F2 Class), fatigue assessment can<br />

therefore be proceeded. Figure 45 illustrates the fatigue damage assessment result. <strong>The</strong> estimate fatigue life at<br />

the fatigue assessment point considered is 713 years, which is greater than the design fatigue life of 200~500<br />

years.<br />

3.4.8 Permanent Loads Monitoring (Figures 46-47)<br />

<strong>The</strong> results of permanent loads monitoring at Stonecutters tower-base is shown in Figures 46 and 47. <strong>The</strong> total<br />

measured compressive strains in Locations A and B of Figure 46 are 626 με and 651 με respectively at a<br />

reference concrete temperature of 20°C. <strong>The</strong> strain analysis shows that the percentages of structural strain, creep<br />

strain and shrinkage strain are respective 44%, 20% and 36% (upon the bridge opening to public traffics). <strong>The</strong><br />

strain due to permanent loads is around 44% of the total measured compressive strains or 281 με (=44%<br />

x(626+651)/2). This strain corresponds to 8.486 MPa ≈ 8.392 MPa which is estimated basing on self-weight of<br />

concrete (71250 tons), stainless steel (1400 tons), steel reinforcement (5500 tons), self-weight of steel deck and<br />

stay cables (20100 tons per tower), pavement (2126 tons), street furniture (277 tons) and a tower-area of 119.94<br />

m 2 at 5.8 mPD or the strain instrument level.<br />

-255-