2. General<br />

2.1 Application / Installation<br />

The Aqualift F Pumpstation is designed to automatically pump<br />

wastewater (with or without sewage collected below the outgoing<br />

sewer level) according to the requirement of DIN 1986<br />

into a septic system or public sewer piping. This system is only<br />

for use with wastewater draining from single and multi-family<br />

homes, commercial buildings, hotels, restaurants, hospitals,<br />

schools or similar buildings. In circumstances where the interruption<br />

of wastewater flow is not allowed or desired, a twin<br />

pump system (Pumpstation Aqualift F Duo) is required in which<br />

the second pump will activate during times of heavy flow or if<br />

the second pump is not operating for any reason.<br />

The KESSEL Pumpstation Aqualift F is designed for outdoor /<br />

underground installation. Pumps are equipped with macerating<br />

blades which cut all soft objects into smaller pumpable pieces.<br />

Due to the cutting blades, outlet pipes of DN 40 or larger may<br />

be connected to the outlet of the Pumpstation<br />

Aqualift F. Objects in the wastewater which could damage or<br />

cause wear and tear on the cutting / macerating blades should<br />

not come in contact with the pumps. The system is designed<br />

to handle continuous wastewater temperatures up to 40 deg C<br />

(104 deg F).<br />

The KESSEL Aqualift F Pumpstation is delivered in the following<br />

variations:<br />

• As a mono unit with a single pump or as a duo unit with twin<br />

pumps<br />

• With pumps with various strengths (kW)<br />

• In a KESSEL Inspection Chamber with an internal width of<br />

800mm or 1000mm<br />

• With installation depths from 1.5 to 5.0 meters<br />

The pump base, gate closure valves, non-return flaps, pressure<br />

pipe connection and float switches have already been<br />

installed in the chamber base. The pumps, the additional inspection<br />

chamber sections and the control unit are delivered<br />

not installed in the system. Depending on the size of the<br />

pumps, the pumps are either delivered inside the chamber’s<br />

upper section or on a separate pallet. The pumps should be<br />

installed in the chamber only after the chamber has been<br />

completely installed.<br />

EX<br />

In order allow any collecting explosive gases<br />

to disperse, adequate ventilation is required.<br />

2.2 Aqualift F description<br />

The KESSEL Aqualift F pumpstation consists of the following:<br />

1. Single (1 pump) or Twin (2 pumps)<br />

2. In KESSEL 800 or 1000mm diameter Inspection Chamber<br />

3. Pump support base<br />

4. Closure valve for each pump<br />

5. Backflow flap<br />

6. PEHD PN 10 pressure outlet in size DN 50 (OD 63mm)<br />

and DN 80 (OD 90mm)<br />

7. DN 100 ventilation connection<br />

8. DN 100 cable connection<br />

9. DN 100 / DN 150 inlet<br />

10. Float switches<br />

11. Control unit (see illustration in Chapter 8)<br />

8<br />

7<br />

9<br />

2<br />

4<br />

6<br />

5<br />

1<br />

3<br />

10<br />

Illustration shows KESSEL Pumpstation Aqualift F<br />

twin pumping unit<br />

42