5. Electrical Connections<br />
TWIN PUMP SYSTEMS – FOLLOW ALL SAFETY REGULATIONS!<br />
Required work Control units from Jan 2010 and newer Control units up to December 20<strong>09</strong><br />
Float switch connections -<br />
“Off”, “On” and “Alarm”<br />
The cable ends of the float switches are to<br />
be connected to the appropriate connection<br />
jacks in the HAZARD area inside the<br />
control unit which are protected by the electrical<br />
shield (see connection plan)<br />
• The float switch cables should be connected<br />
to the appropriate marked jacks<br />
• The connection jacks of the floats switches<br />
may not be connected to any other circuits.<br />
• The jacks are marked with the switch symbol.<br />
Warning and Alarm<br />
outputs<br />
• The ‘Störung’ (malfunction) and ‘Alarm’<br />
(alarm) control unit signals are controlled<br />
by a relay. Inductive loads must be externally<br />
eliminated. The stand by (powerless)<br />
position of the relays is printed<br />
on the board. This means the ‘Warning’<br />
and ‘Alarm’ signals are activated<br />
• 42 V ac dc / 0.5 Amps<br />
• The ‘Störung’ (malfunction) and ‘Alarm’<br />
(alarm) control unit signals are controlled<br />
by a relay. Inductive loads must be externally<br />
eliminated. The stand by (powerless)<br />
position of the relays is printed on the<br />
board. This means the ‘Warning’ and<br />
‘Alarm’ signals are activated<br />
• The relay contacts have absolutely no<br />
connection to the supply or operating<br />
power and are separated from this up to<br />
300 volts according to Table D.10 of the EN<br />
61010 norm<br />
• The relays are designed to switch a 230<br />
volt / 2 Amp source. The current is to be externally<br />
limited to these values.<br />
• It is not allowed to switch phases with the<br />
relays. The phase may deviate from L1.<br />
Outputs L1 / N<br />
(230V / 50 Hz)<br />
• The outputs N / L1 (2 each) are designed<br />
to activated malfunction or alarms<br />
via the relays. They should not be used<br />
for any other purpose.<br />
• The maximum allowable current is 2<br />
Amps.<br />
56