5. Electrical Connections<br />

TWIN PUMP SYSTEMS – FOLLOW ALL SAFETY REGULATIONS!<br />

Required work Control units from Jan 2010 and newer Control units up to December 20<strong>09</strong><br />

Float switch connections -<br />

“Off”, “On” and “Alarm”<br />

The cable ends of the float switches are to<br />

be connected to the appropriate connection<br />

jacks in the HAZARD area inside the<br />

control unit which are protected by the electrical<br />

shield (see connection plan)<br />

• The float switch cables should be connected<br />

to the appropriate marked jacks<br />

• The connection jacks of the floats switches<br />

may not be connected to any other circuits.<br />

• The jacks are marked with the switch symbol.<br />

Warning and Alarm<br />

outputs<br />

• The ‘Störung’ (malfunction) and ‘Alarm’<br />

(alarm) control unit signals are controlled<br />

by a relay. Inductive loads must be externally<br />

eliminated. The stand by (powerless)<br />

position of the relays is printed<br />

on the board. This means the ‘Warning’<br />

and ‘Alarm’ signals are activated<br />

• 42 V ac dc / 0.5 Amps<br />

• The ‘Störung’ (malfunction) and ‘Alarm’<br />

(alarm) control unit signals are controlled<br />

by a relay. Inductive loads must be externally<br />

eliminated. The stand by (powerless)<br />

position of the relays is printed on the<br />

board. This means the ‘Warning’ and<br />

‘Alarm’ signals are activated<br />

• The relay contacts have absolutely no<br />

connection to the supply or operating<br />

power and are separated from this up to<br />

300 volts according to Table D.10 of the EN<br />

61010 norm<br />

• The relays are designed to switch a 230<br />

volt / 2 Amp source. The current is to be externally<br />

limited to these values.<br />

• It is not allowed to switch phases with the<br />

relays. The phase may deviate from L1.<br />

Outputs L1 / N<br />

(230V / 50 Hz)<br />

• The outputs N / L1 (2 each) are designed<br />

to activated malfunction or alarms<br />

via the relays. They should not be used<br />

for any other purpose.<br />

• The maximum allowable current is 2<br />

Amps.<br />