Level malfunction<br />

Duo Pumpe 1/2<br />

8. Problems and Solutions<br />

• Level malfunction<br />

A float switches has activated without one of the float switches below activating first<br />

(incorrect order of float switch activation)<br />

--> Check all float switch cables to make sure they are not tangled or wrapped up.<br />

Make sure all float switches can move freely<br />

--> Check float switches for proper operation<br />

Single Pump Aqualift F<br />

• “Pump Off“ float switch which does not activate.<br />

In the case that the ”Pump Off” float switch does not shut off,<br />

the alarm warning will be activated when the wastewater<br />

level rises above the ”Pump On“ level. The pump will turn off<br />

when the wastewater level falls below the ”Pump On“ level.<br />

• “Pump On” float switch which does not activate.<br />

The alarm will activate and the pump will start when the wastewater<br />

rises above the ”Alarm On” level. Pump will turn off<br />

when the level falls below the ”Pump On” level.<br />

• “Pump On” float switch which is stuck in the “On” position.<br />

A warning will be displayed after the wastewater falls below<br />

the “Pump Off” level. The pump remains in activation.<br />

• “Alarm” float switch is stuck in the “On” position.<br />

A warning will be displayed after the wastewater level has fallen<br />

below the “Pump On” level – the warning will be a continuous<br />

(non-stop) alarm warning. The alarm can be acknowledged<br />

by pressing the Alarm button. The warning relay will<br />

remain activated until the problem has been cleared / fixed.<br />

The pump continues to run. A level malfunction warning<br />

occurs .<br />

Double Pump Aqualift F<br />

• “Pump Off” float switch which does not activate.<br />

Malfunction warning occurs when the Pump 1 On level exceeded.<br />

Both pumps activate only when the wastewater level<br />

exceeds the Pump 2 On level and turn off when the level falls<br />

below the Pump 1 On level<br />

• “Pump On” float switch which does not activate.<br />

Malfunction warning occurs after wastewater level falls<br />

below the Pump Off level. The pumps remain in operation. A<br />

level malfunction warning occurs<br />

• Constantly closed “Pump 1 On” level switch.<br />

An alarm will activate after the wastewater level has fallen<br />

below the “Pumps Off” level. Both pumps will continue to run.<br />

A level malfunction warning occurs.<br />

• Constantly closed “Pump 2 On” level switch.<br />

An alarm will activate after the wastewater level has fallen<br />

below the “Pumps Off” level. Both pumps will continue to run.<br />

A level malfunction warning occurs.<br />

• Constantly closed ”Alarm” level switch.<br />

Malfunction warning occurs after the wastewater level falls<br />

below the ‘Pump On’ level. A continuous alarm sounds. The<br />

alarm can be acknowledged by pressing the Alarm button.<br />

The warning relay will remain activated until the problem has<br />

been cleared / fixed. The pump continues to run. A level malfunction<br />

warning occurs<br />

8.3 Disturbances / Internal controls<br />

The control unit continuously monitors motor temperature,<br />

the motor protection switch and the rotation / phase of the<br />

motors. In the case of a disturbance the pump will either be<br />

shut off or prevented from starting. This will result in a corresponding<br />

alarm and the lighting of an LED.<br />

8.3.1 Phase / Rotation Monitoring<br />

In the case that L2 and / or L3 fail, the ”Phase/Drehfeld” LED<br />

will continuously light and the ”Störung” relay will activate.<br />

Since the control of L1 is still active, the failure of L1 will not<br />

be displayed. In the case that L1 fails the installed warning<br />

device will sound as long a battery has been installed in the<br />

control unit. In the case that the rotation is incorrect, the<br />

”Phase / Drehfeld” LED will blink.<br />

In the operational mode ”Hand” it is possible to run the pump<br />

with the incorrect rotation – in all other operational modes the<br />

control unit will block the functioning of the motor in the case<br />

that the rotation is incorrect.<br />

• “Pump 2 On” float switch which does not activate.<br />

An alarm will activate after the wastewater level has fallen<br />

below above the “Pump Off” level. Both pumps will continue<br />

to run. A level malfunction warning occurs<br />

67