5. Electrical connections<br />

5.6 Controls<br />

Checking the motor protection switches<br />

The motor protection switch must be set for the appropriate<br />

rated current of the pumps – as described<br />

in Section 3 of this manual.<br />

5.7 Completion of electrical work<br />

After all electrical connection work has been completed in the<br />

control unit, the control unit cover must be closed and properly<br />

secured. In order to eliminate odour nuisances in the<br />

area where the control unit is installed, the conduit pipe to the<br />

control unit should be sealed with a special gaskets or simply<br />

with insulation foam.<br />

5.8 Control unit configuration (Models Jan 2010 and newer)<br />

The DIP switches are in the upper right portion of the control unit and have been set at the factory. Due to the explosion<br />

proof rating antiblocking mechanism has been switched off (switch 4) and must not be activated!<br />

1 2 3 4<br />

1. Switch: Sensor<br />

• Switch 1 up: Level measuring with float switches<br />

• Switch 1 down: Level measuring with pressure switch<br />

2. Switch: Level heights<br />

• Switch 2 up: Pumpstation (underground pumpstation)<br />

• Switch 2 down: Lifting station (floor mounted or dry mount inside chamber)<br />

3. Switch: This switch for customer service partners only<br />

4. Switch: Anti blocking function<br />

• Switch 4 up: anti blocking off<br />

• Switch 4 down: anti blocking on<br />

5.9 Control unit configuration (Models December 20<strong>09</strong> and older)<br />

The control unit configuration is set at the factory using switches S601 to S 604 which are between the levels switch connection<br />

jacks and the thermal protection inputs. These should be checked using the table below to make sure they are correct<br />

– the proper settings are marked in grey.<br />

– The four DIP switches (switch S604) are set at the factory and should not be changed.<br />

Models December<br />

20<strong>09</strong> and older<br />

S604 / 1<br />

S604 / 2<br />

S604 / 3<br />

S604 / 4<br />

ON<br />

running time control<br />

(lifting station)<br />

Submersible pump<br />

without OFF float switch<br />

Rotation / Phase controlled<br />

On<br />

Anti blocking function<br />

On<br />

OFF<br />

level controlled<br />

(submersible pump station)<br />

Submersible pump<br />

with OFF float switch<br />

Rotation / Phase controlled<br />

Off<br />

Anti blocking function<br />

Off<br />