8. Problems and Solutions<br />

8.3.2 Motor Protection Switch<br />

In the case that a motor protection switch is activated either<br />

manually, by a short circuit or by an overload, a malfunction<br />

warning will be displayed and the malfunction relay will activate.<br />

8.3.3 Motor temperature<br />

Each motor of the Pumpstation Aqualift F is equipped with<br />

two temperature sensors which send data to the control unit.<br />

• Temperature (not recorded) – TF1a (TF2a)<br />

• Temperature (recorded) – TF1b (TF2b)<br />

In the case that temperature level TF1a has been reached it<br />

will be displayed on the control unit and the malfunction relay<br />

switch will activate. Also the control unit will shut down the<br />

pumps. As soon as the pumps cool down they will return to<br />

normal operation.<br />

In the case that temperature level TF1b has been reached it<br />

will be displayed on the control unit and the malfunction relay<br />

switch will activate. Also the control unit will shut down the<br />

pumps. As soon as the pumps cool down they will return to<br />

normal operation. The control unit will attempt to restart the<br />

pumps up to 30 times per every 2 minute period. The Temperature<br />

TF1b will not be stored in the control unit’s memory<br />

in the case of a power failure.<br />

In the case that the malfunction cannot be cleared, it is probable<br />

that the pump(s) are damaged and need to be replaced.<br />

Notice:<br />

In the case that the TF1b is exceeded and simultaneously the<br />

Alarm level is reached the following applies:<br />

• Press the Alarm button once will turn off the audible alarm<br />

• Press the Alarm button a second time to acknowledge the<br />

alarm (resets the alarm)<br />

8.4 Displayed Warnings<br />

Warnings will occur by:<br />

• the activation of the failure relay and the connected warning<br />

device.<br />

• display of the type of failure by LEDs on the control unit resulting<br />

From:<br />

Single pump units<br />

- Phase / rotation problems<br />

- Motor protection switch<br />

- Motor temperature<br />

- Running times / level<br />

- Relay error<br />

- Battery error<br />

- Power error<br />

- Level error<br />

- Maximum run time error<br />

- Maximum pump start/stop error<br />

Twin pump systems:<br />

- Phase / rotation problems<br />

- Motor protection switch<br />

- Motor temperature<br />

- Running times / level<br />

- Relay error<br />

- Battery error<br />

- Power error<br />

- Level error<br />

- Maximum run time error<br />

- Maximum pump start/stop error<br />

Conditions which can cause a warning to be displayed are<br />

individually listed in this manual<br />

8.5 ”Alarm” warnings<br />

Alarm warnings occur from:<br />

• the activation of the Alarm relay and the connected warning<br />

device<br />

• the internal signal sender<br />

Two situations can result in an alarm warning:<br />

1.The wastewater level inside the chamber rises above the<br />

level of the ”Alarm” float switch. The audible alarm can be<br />

turned off by pressing the ”Alarm” button. As soon as the<br />

wastewater has fallen below the ”Alarm” float level both<br />

alarms (signal and relay) will be cancelled.<br />

2. If a loaded battery is placed in the control unit, an audible<br />

alarm will be activated in the case of a power failure. This<br />

audible alarm will continue for several hours depending on<br />

the power in the battery. This alarm can be cancelled by<br />

pressing the ”Alarm” Reset button.<br />

8.6 What to do when…<br />

...The motor protection switch has activated -<br />

Open the control unit and reactivate the motor protection<br />

switch.<br />

...A different warning signal activates –<br />

in the case that a warning signal cannot be cleared by<br />

using the instructions in this manual, please contact a<br />

licensed electrician.<br />

...The Aqualift F no longer reacts to incoming signals -<br />

unplug the control unit of the Aqualift F for at least 10 seconds<br />

and then plug back in. In the case that the Aqualift<br />

no longer responds to incoming signal please contact a licensed<br />

professional<br />