Table 11.4 Transmission loss and STC values for common partitions<br />

Building <strong>Acoustics</strong> 11.1 Room <strong>Acoustics</strong> 397<br />

Partition 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz STC<br />

1/2 inch drywall on both 17 31 33 40 38 36 33<br />

sides of wooden studs<br />

1/2 inch drywall on wooden 15 30 34 44 46 41 37<br />

studs with 2 inches of insulation<br />

Double layer of 1/2inch 25 34 41 51 48 50 41<br />

drywall on wooden studs<br />

1/2inchdrywallon 23 28 39 46 54 44 39<br />

staggered wooden studs<br />

1/2 inch drywall on staggered 29 38 45 52 58 50 48<br />

wooden studs with 2 inches of insulation<br />

1/2 inch drywall on metal studs 22 27 43 47 37 46 39<br />

1/2 inch drywall on metal studs 26 41 52 54 45 51 45<br />

with 2 inches of insulation<br />

8 inch thick concrete 36 44 50 54 58 56 53<br />

masonry units<br />

Open-plane office partition 10 12 12 12 12 11 12<br />

4 inch thick brick wall 32 34 40 47 55 61 45<br />

1/2inchdrywallinside/1inch 21 33 41 46 47 51 42<br />

stucco outside on wooden studs<br />

Single-paned 1/8 inch thick glass 18 21 26 31 33 22 26<br />

1/2 inch thick laminated glass 31 34 38 40 37 46 40<br />

Double-paned 1/8 inch thick 13 25 35 44 49 43 37<br />

glasswith2inchairgap<br />

Hollow wooden door, 1 3/4inchthick 14 19 23 18 17 21 19<br />

Solid wooden door, 1 3/4inchthick 29 31 31 31 39 43 34<br />

Hollow metal door, 1 3/4inchthick 24 23 29 31 24 40 28<br />

Filled metal door, 1 3/4inchthick 26 34 40 48 44 52 43<br />

Wood joist floor/ceiling with 1/2inch 23 32 36 45 49 56 37<br />

plywood subfloor and 1/2inchdrywall<br />

8 inch thick concrete slab floor 32 38 47 52 57 63 50<br />

Wood plank shingled roof 29 33 37 44 55 63 43<br />

Wood plank shingled roof with 1/2inch 35 42 49 62 67 79 53<br />

drywall ceiling, 4 inches of insulation<br />

Corrugated steel roof with 1 inch 17 22 26 30 35 41 30<br />

of sprayed cellulose<br />

E 989. The IIC stresses the low-frequency range, as<br />

isshowninFig.11.16, but note that IIC does not address<br />

very low (below 100 Hz) frequencies, which may<br />

be associated with resonances of a building’s structural<br />

components.<br />

One other single-number rating worth noting here<br />

is the outdoor–indoor transmission class (OITC), established<br />

in ASTM E 1332. The OITC is a single-number<br />

rating for the effectiveness of a building façade in reducing<br />

noise <strong>to</strong> interior spaces. The calculation of OITC<br />

is based on an A-weighted source spectrum of typical<br />

transportation (aircraft, rail, and traffic) sources in the<br />

80–4000 Hz range and the façade’s transmission loss<br />

spectrum in the same frequency range.<br />

Non-Homogeneous Partitions<br />

Up <strong>to</strong> this point we have been discussing homogeneous<br />

partitions. Actual designs, however, include walls composed<br />

of different materials, such as those with windows<br />

and doors. Each of these wall components has different<br />

associated TL characteristics. Wall components having<br />

lower TL characteristics than the rest of the wall can<br />

significantly degrade a wall’s sound reduction effectiveness.<br />

This can be calculated using the composite<br />