MITIGATION<br />

Receptor Quiet Daytime LA90, 10 min Night-time LA90, 10 min<br />

Brampton Villa (H6) 28.0 – 67.6 24.9 – 57.1<br />

Aston (H7) 26.9 – 52.9 21.1 – 49.5<br />

Hardwick (H8) 28.4 – 60.3 25.0 – 54.9<br />

9.26 The exact model of turbine to be used at the site will be the result of a<br />

future tendering process. Achievement of the noise limits determined by<br />

this assessment will be a key determining factor in the final choice of<br />

turbines <strong>for</strong> the site. Predictions of wind turbine noise have been made,<br />

based upon sound power level data <strong>for</strong> the REpower 3.3M wind turbine<br />

and a noise prediction model procedure that can be considered to be<br />

worst-case. Full noise data <strong>for</strong> the REpower 3.3M is not yet available so it<br />

has been assumed <strong>for</strong> the purposes of this assessment that octave data<br />

<strong>for</strong> another REpower turbine, the MM92 2.0MW is comparable. The octave<br />

data has been increased uni<strong>for</strong>mly <strong>for</strong> each band so that the total sound<br />

power level is equal to that stated <strong>for</strong> the REpower 3.3M. For<br />

completeness the MM92 has also been modelled and it has been shown<br />

that the REpower 3.3M is louder at all windspeeds (as shown in Appendix<br />

5, Figures 5.1-5.8). All results tables have there<strong>for</strong>e been based on the<br />

REpower 3.3M noise data.<br />

PREDICTED EFFECTS<br />

9.27 Noise levels arising from the operation of the proposed wind farm were<br />

calculated using the propagation model contained within Part 2 of<br />

“International Standard ISO 9613-2, Acoustics – Attenuation of Sound<br />

during Propagation Outdoors”. The model uses as its acoustic input data<br />

the octave band sound power output of a turbine suitable <strong>for</strong> this<br />

development (in this case the Repower 3.3M 3.3MW machine) and<br />

calculates, on an octave band basis, attenuation due to geometric<br />

spreading, atmospheric absorption and ground effects. The noise model<br />

was set up to provide worst case noise predictions, including hard ground<br />

attenuation, no barrier effects, and low levels of atmospheric attenuation.<br />

Changes in wind shear between daytime and night-time periods were also<br />

included in the predictions.<br />

9.28 The assessment of the proposed wind farm noise is contained within<br />

Section 5 of the Noise Assessment (Appendix 5). This provides an<br />

assessment of the wind farm in accordance with the requirements of<br />

ETSU-R-97. The assessment is summarised in Tables 9.3 and 9.4.<br />

215<br />

Penny Hill Wind Farm<br />

Environmental Statement