Moravian Preservation Master Plan.indb - Society for College and ...
Moravian Preservation Master Plan.indb - Society for College and ...
Moravian Preservation Master Plan.indb - Society for College and ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Moravian</strong> <strong>College</strong> • <strong>Preservation</strong> <strong>Master</strong> <strong>Plan</strong><br />
system or scupper, which in turn directs water to<br />
an internal or external downspout. The downspout<br />
carries water down to the foundation <strong>and</strong> directs<br />
runoff into an underground drain, French drain,<br />
grade level channel, or splash block in order to<br />
move the water away from the building foundation.<br />
Ideally, the roof <strong>and</strong> roof drainage system, from<br />
rooftop to site or storm sewer, is designed <strong>and</strong><br />
maintained as one system.<br />
Typical Roof <strong>and</strong> Roof Drainage<br />
System Conditions<br />
Roofs throughout the <strong>Moravian</strong> <strong>College</strong> campus<br />
include a variety of materials <strong>and</strong> shapes ranging<br />
from gambrel to gabled to flat. Roofing materials<br />
include traditional slate or wood shingle, as well<br />
as modern asphalt shingle, built-up, <strong>and</strong> EPDM<br />
roofing. Ornamental features, such as dormers,<br />
belvederes, <strong>and</strong> cupolas, add visual interest. Roofs<br />
typically drain to hanging half-round gutters<br />
<strong>and</strong> round downspouts, which drain either to<br />
underground drain lines or to grade. In a few cases,<br />
the roofs drain directly to grade with no provision<br />
<strong>for</strong> roof-edge collection.<br />
Roofing materials are undergoing minor<br />
deterioration, particularly at slate roofs where<br />
slates are loose, broken, or missing. On a few<br />
buildings, gypsum can be seen as a white crust on<br />
slate surfaces, which is an indication of long-term<br />
weathering <strong>and</strong> approaching end-of-life service<br />
<strong>for</strong> the material. Metal flashing is rusting in a few<br />
locations. Roof leaks have led to damage in some<br />
interior spaces <strong>and</strong> deterioration of exterior walls.<br />
The most severe <strong>and</strong> prevalent problems of roofs<br />
at <strong>Moravian</strong> <strong>College</strong> are related to problematic<br />
roof drainage systems. Gutters are bent, clogged,<br />
or inadequately sloped <strong>and</strong> chronically overflow.<br />
In a few places, entire downspouts or bottom<br />
sections of downspouts are missing. Where<br />
they are intact, downspouts fail to direct water<br />
away from the building foundations because of<br />
inadequate or clogged underground drainage,<br />
or because they release water at points that are<br />
close or directly against the building foundation.<br />
Deteriorated masonry, open or eroded masonry<br />
joints, rising damp in masonry walls, salts <strong>for</strong>ming<br />
on masonry surfaces, biological growth, wood rot,<br />
ponding water, <strong>and</strong> soil erosion are indicative of<br />
long-st<strong>and</strong>ing issues <strong>and</strong> a general lack of focused<br />
cyclical maintenance.<br />
In the few locations where the roofs are designed<br />
to drain directly to the ground, site drainage must<br />
often be improved. Underground drain lines are<br />
frequently clogged. Many underground lines are<br />
composed of terra-cotta pipe that becomes broken<br />
or displaced through ground movement <strong>and</strong> root<br />
action.<br />
The relatively simple task of regular inspection is an<br />
urgent priority: the gutters <strong>and</strong> downspouts of all<br />
historic buildings should be inspected <strong>and</strong> cleaned<br />
at least twice yearly. Moisture-related problems<br />
affecting roof systems should be properly diagnosed<br />
<strong>and</strong> corrected at their source. Missing, bent,<br />
sagging, <strong>and</strong> inadequately sloped gutters should<br />
be replaced. Missing downspout components must<br />
be replaced immediately or temporary measures<br />
installed to redirect water drainage. Problems with<br />
site drainage must be holistically investigated <strong>and</strong><br />
properly addressed in order to improve conditions<br />
at building foundations. Roof <strong>and</strong> roof drainage<br />
system work should become a priority <strong>and</strong> should<br />
be accompanied by implementation of cyclical<br />
maintenance <strong>and</strong> monitoring.<br />
Roof <strong>and</strong> Roof Drainage System<br />
Inspection<br />
The best course of action in maintaining a roof<br />
<strong>and</strong> its drainage system is periodic inspection <strong>and</strong><br />
repair. The baseline roof inspection should include<br />
a yearly inspection of the entire roof system <strong>and</strong><br />
twice-yearly removal of debris from gutters <strong>and</strong><br />
downspouts. The yearly evaluation should be<br />
comprehensive <strong>and</strong> examine not only exteriors,<br />
but also the attic, basement, <strong>and</strong> crawl spaces. Roof<br />
components such as flashing, gutters, downspouts,<br />
hatches, <strong>and</strong> mechanical equipment should be part<br />
of this inspection. Inspection should include testing<br />
<strong>and</strong>/or observation during major rain events to<br />
ensure that the roof drainage system successfully<br />
diverts rainwater away from the building.<br />
Underground drains are especially susceptible to<br />
failure, largely because they are difficult to inspect<br />
<strong>and</strong> maintain. Remote inspection techniques are<br />
often required, such as a flexible rod equipped with<br />
a radio transmitter or fiber optic camera. By the time<br />
problematic conditions are detected, substantial <strong>and</strong><br />
expensive damage may have occurred. There<strong>for</strong>e,<br />
the first line of defense is regular roof inspection.<br />
A roof system in good condition should meet all of<br />
the following criteria during inspection.<br />
John Milner Associates • October 2009 • Chapter 9 • Building Guidelines • 299