system and shall be in accordance with UFC Article 10, NFPA 17A and NFPA<br />

96. Provide a Class “K” type portable fire extinguisher within 30 feet the kitchen<br />

appliances emitting grease-laden vapors.<br />

120. Every building and/or business suite is required to post address numbers that are<br />

visible from the street and alley. Address numbers shall be a minimum <strong>of</strong> six (6)<br />

inches in height and contrast with their background. Suite or room numbers shall<br />

be a minimum <strong>of</strong> four (4) inches in height and contrast with their background.<br />

<strong>Santa</strong> <strong>Monica</strong> Municipal Code Chapter 8 Section 8.48.130 (l) (1)<br />

121. When more than one exit is required they shall be arranged so that it is possible to<br />

go in either direction to a separate exit, except deadends not exceeding 20 feet,<br />

and 50 feet in fully sprinklered buildings.<br />

122. Exit and directional signs shall be installed at every required exit doorway,<br />

intersection <strong>of</strong> corridors, exit stairways and at other such locations and intervals<br />

as necessary to clearly indicate the direction <strong>of</strong> egress. This occupancy/use<br />

requires the installation <strong>of</strong> approved floor level exit pathway marking. Exit doors<br />

shall be openable from the inside without the use <strong>of</strong> a key, special effort or<br />

knowledge.<br />

123. Show ALL door hardware intended for installation on Exit doors.<br />

124. In buildings two stories or more in height an approved floor plan providing<br />

emergency procedure information shall be posted at the entrance to each stairway,<br />

in every elevator lobby, and immediately inside all entrances to the building. The<br />

information shall be posted so that it describes the represented floor and can be<br />

easily seen upon entering the floor level or the building. Required information<br />

shall meet the minimum standards established in the <strong>Santa</strong> <strong>Monica</strong> Fire<br />

Department, Fire Prevention Division, information sheet entitled “Evacuation<br />

Floor Plan Signs.” (California Code <strong>of</strong> Regulations Title 19 Section 3.09)<br />

125. Stairway Identification shall be in compliance with CBC 1022.8<br />

126. Floor-level exit signs are required in Group A, E, I, R-1, R-2 and R-4<br />

occupancies.<br />

127. In buildings two stories in height at least one elevator shall conform to the<br />

California Building Code Chapter 30 section 3003.5a for General Stretcher<br />

Requirements for medical emergency use.<br />

a. The elevator entrance shall not be less than 42 inches wide by 72 inches<br />

high.<br />

b. The elevator car shall have a minimum clear distance between walls<br />

excluding return panels <strong>of</strong> not less than 80 inches by 54 inches.<br />