TABLE 1 *<br />

BUILDING SIZE<br />

(First floor area)<br />

Under 3,000<br />

3,000 to 4,999<br />

sq. ft.<br />

sq. ft.<br />

sq. ft.<br />

sq. ft.<br />

sq. ft.<br />

Fire Flow *(1) (2) Duration Hydrant Spacing<br />

1,000 GPM 2 hrs.<br />

300 ft.<br />

1,250 GPM 2 hrs.<br />

300 ft.<br />

5,000 to 7,999<br />

1,500 GPM<br />

2 hrs.<br />

300 ft.<br />

15,000 to 19,999<br />

20,000 to 24,999<br />

sq. ft.<br />

sq. ft.<br />

sq. ft.<br />

sq. ft.<br />

sq. ft.<br />

3,000 GPM<br />

3,500 GPM<br />

3 hrs.<br />

3 hrs.<br />

300 ft.<br />

300 ft.<br />

25,000 to 29,999<br />

4,000 GPM<br />

4 hrs.<br />

300 ft.<br />

* See applicable footnotes below:<br />

(FIRE FLOWS MEASURED AT 20 POUNDS PER SQUARE INCH<br />

RESIDUAL PRESSURE)<br />

(1) Conditions requiring additional fire flow.<br />

a. Each story above ground level - add 500 GPM per story.<br />

b. Any exposure within 50 feet - add a total <strong>of</strong> 500 GPM.<br />

c. Any high-rise building (as determined by the jurisdictional building code)<br />

the fire flow shall be a minimum <strong>of</strong> 3,500 GPM for 3 hours at 20 psi.<br />

d. Any flow may be increased up to 1,000 GPM for a hazardous occupancy.<br />

(2) Reductions in fire flow shall be cumulative for type <strong>of</strong> construction and a fully<br />

sprinklered building. The following allowances and/or additions may be made<br />

to standard fire flow requirements:<br />

105<br />

F:\RECORDSANDELECTIONSHARE\MEETINGS\WWW\2013\20130514\WORD DOCUMENTS\2013051407-A-2.DOC