a. The minimum clear width shall be not less than 20 feet. No parking,<br />

stopping or standing <strong>of</strong> vehicles is permitted in this clear width.<br />

b. When fire hydrants or fire department connections to fire sprinkler<br />

systems are located on fire apparatus access roads the minimum width<br />

shall be 26 feet. This additional width shall extend for 20 feet on each side<br />

<strong>of</strong> the centerline <strong>of</strong> the fire hydrant or fire department connection.<br />

c. The minimum vertical clearance shall be 13 feet, 6 inches.<br />

d. The minimum turn radius for all access road turns shall be not less than 39<br />

feet for the inside radius and 45 feet for the outside radius.<br />

e. Dead-end access roads in excess <strong>of</strong> 150 feet in length shall be provided<br />

with either a 96 feet diameter “cul-de-sac,” 60 foot “Y” or 120-foot<br />

“hammerhead” to allow the apparatus to turn.<br />

f. The surface shall be designed and maintained to support the imposed loads<br />

<strong>of</strong> at least 75,000-pound and shall be “all-weather.” An “all-weather”<br />

surface is asphalt, concrete or other approved driving surface capable <strong>of</strong><br />

supporting the load.<br />

136. Gates installed on fire apparatus access roads shall comply with the following:<br />

a. The width <strong>of</strong> any gate installed on a fire apparatus access road shall be a<br />

minimum <strong>of</strong> 20 feet.<br />

b. Gates may be <strong>of</strong> the swinging or sliding type.<br />

c. Gates shall be constructed <strong>of</strong> materials that will allow for manual<br />

operation by one person.<br />

d. All gate components shall be maintained in an operative condition at all<br />

times and shall be repaired or replaced when defective.<br />

e. Electric gates shall be equipped with a means <strong>of</strong> opening the gate by fire<br />

department personnel for emergency access. The Fire Prevention Division<br />

shall approve emergency opening devices.<br />

f. Manual opening gates may be locked with a padlock, as long it is<br />

accessible to be opened by means <strong>of</strong> forcible entry tools.<br />

g. The Fire Prevention Division shall approve locking device specification.<br />