Chapter 6 - Parameter Description [I/O]Output FrequencyI/O-42I/O-43 / 2Time[OL]AXA-AXC is CLOSED when the output current hasreached the FU1-54 [Overload Warning Level] for theFU1-55 [Overload Warning Time].Output CurrentFU1-54[OL level]AXA-AXCONON[AXA-AXC configured as ‘FDT-3’]TimeFU1-54[OL level]Time[FDT-4]AXA-AXC is CLOSED when the output frequencyreaches the FDT frequency. The output is OPENEDwhen the output frequency goes below the FDTbandwidth centered on the FDT frequency.Output FrequencyAXA-AXCRelated Functions:t1ONt1[AXA-AXC configured as ‘OL’]Timet1: FU1-55 [Overload Warning Time]FU1-54 [Overload Warning Level]FU1-55 [Overload Warning Time]I/O-42AXA-AXCCLOSEDI/O-43 / 2TimeTime[IOL]AXA-AXC is CLOSED when the output current is abovethe 150% of rated inverter current for 36 seconds. If thissituation is continued for one minute, the inverter will cutoff its output and displays ‘IOL’ (Inverter overload) Trip.See the nameplate for the rated inverter current.[AXA-AXC configured as ‘FDT-4’]Output Current[FDT-5]This is the inverted output of [FDT-4].Output Frequency150% of RatedInverter Current150% of RatedInverter CurrentTimeI/O-42AXA-AXCONI/O-43 / 2TimeONTimeAXA-AXCON36sec24sec[AXA-AXC configured as ‘IOL’]Time[AXA-AXC configured as ‘FDT-5’]130