Chapter 6 - Parameter Description [I/O][Stall]AXA-AXC is CLOSED when the inverter is on the stallprevention mode.Output CurrentFU1-60[Stall Level]FU1-60[Stall Level]Output FrequencyAXA-AXCRelated Functions:[AXA-AXC configured as ‘Stall’]TimeTime[OV]AXA-AXC is CLOSED when the DC link voltage is abovethe Over-voltage level.DC Link VoltageCLOSEDFU1-59 [Stall Prevention Mode]FU1-60 [Stall Prevention Level]TimeOV Level (380V DC or 760V DC)[OH]AXA-AXC is CLOSED when the heat sink of the inverteris above the reference level.[Lost Command]AXA-AXC is CLOSED when frequency reference is lost.Related Functions:[Run]AXA-AXC is CLOSED when the inverter is running.[Stop]AXA-AXC is CLOSED when the inverter is stopped.[INV line, COMM line]This function is used in conjunction with ‘Exchange’function of multi-function input for commercial lineexchange. To use both signal of ‘INV line’ and ‘COMMline’, the optional Sub-A or Sub-C board must beinstalled.Output FrequencyI/O-11 [Criteria for Analog Signal Loss]I/O-48 [Operating Method at Signal Loss]I/O-49 [Waiting Time for Time Out]Speed SearchTimeTimeFX-CMONTimeAXA-AXC[AXA-AXC configured as ‘OV’][LV]AXA-AXC is CLOSED when the DC link voltage is belowthe Low-voltage level.DC Link VoltageONTimeLV Level (200V DC or 400V DC)‘Exchange’-CMAXA-AXC‘COMM line’Q1-EXTG‘INV line’ONInverterDrivet1ONONCommercialLine Drivet2InverterDriveONTimeTimeTimet1, t2: 50msec (interlock time)[AXA-AXC configured as ‘COMM line’ and ‘Q1’ as INV line’]TimeRelated Functions:I/O-12 ~ I/O-14 [Multi-function input]- [Exchange]AXA-AXCON[AXA-AXC configured as ‘LV’]Time131

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!