Chapter 2 - OperationOperationAnalog Voltage Input (V1) + Operation via Terminal (FX/RX)Example (2)[Operation condition]-. Control mode: V/F control-. Reference Frequency: 50[Hz] analog input via V1 (Potentiometer)-. Accel/Decel time: Accel – 10 [Sec], Decel – 20 [Sec]-. Drive mode: Run/Stop via FX/RX terminal[Wiring]3PACinputRSTGB1B2UVWIMS/WPotentiometer1[kohm],1/2WFXRXBXRSTJOGP1P2P3CMVRV15GFM5G30A30C30BAXAAXCStep Parameter setting Code Description1 Control Mode Selection FU2-39 Set it to 0 {V/F}.2 Drive Mode DRV-3 Set it to 1 Fx/Rx-1.3 Frequency Mode DRV-4 Set it to 2 V1 Analog input.450[Hz] freq commandsetting5 Accel/Decel time6 Terminal FX7 Terminal RXDRV-0DRV-2DRV-3Set freq command 50[Hz] via V1(potentiometer).Set Accel time to 10 [Sec] in DRV-2.Set Decel time to 20 [Sec] in DRV-3.Motor starts to rotate in Forward direction at 50Hz with Accel time10 [sec] when FX terminal is turned ON.Motor decelerates to stop with Decel time 20[sec] when FXterminal is turned OFF.When RX terminal is turned ON motor starts to rotate in Reversedirection at 50[Hz] with Accel time 10 [Hz]. When it is OFF, motordecelerates to stop with Decel time 20 [Sec].36