Chapter 2 - Operation2.3.1 7-Segment Keypad Display1) Parameter GroupDRV FU1 FU2 I/OEXT2) Parameter Code andOperating Status3) Output Frequency during run,Command Frequency during stopDisplayDescription1) Parameter Group Displays the parameter groups of DRV, FU1, FU2, I/O, EXT, COM, APP groups.Each LED is lit when its parameter group is selected and blinks when the parameter code is located onDRV 20, DRV 21, DRV 22, DRV 23, DRV 24, and DRV 25.2) Parameter Code andOperating Status3) Output Frequency,Command FrequencyDisplays the code of a group. Rotate the encoder knob to move through 0 ~ 99 codes.Displays the operation information.[First digit]F: Forward operationr: Reverse operation[Second digit]d: DC BrakingJ: Jog Terminal Input1~8: Step Frequency Input (Displays the Step of the Auto operation)[Two digits] - mark the reference is lost.PL: Loss of Reference from the Option Board (DPRAM fault)rL: Loss of Reference from the Option Board (Communication network fault)vL: Loss of Analog Frequency Reference (V1: 0~10V)IL: Loss of Analog Frequency Reference (I: 4~20mA)XL: Loss of Reference from the Sub-BoardDisplays the Output Frequency during run.Displays the Command Frequency during stop.29