The Brinch Hansen bearing capacity factors for � � 0� are obtained in the same way as<br />

shown above, giving N c � 5.2, s c � 1.05, d c � 1.3 <strong>and</strong> i c � 0.96.<br />

It is evident from the preceding calculation to obtain q ub that the third term in equation 5.1<br />

is small <strong>and</strong> can be neglected.<br />

Characteristic unit base resistance � 190 � 5.2 � 1.05 � 1.3 � 0.96 � 1294.7 kN/m 2 .<br />

Applying the R1 resistance factor of 1.0, design resistance � R cd � 1294.7 � 13.0 �<br />

3.1 � 52176 kN which is greater than the design action V' d of 30 000 kN.<br />

For <strong>Design</strong> Approach DA1, combination 2 (sets A2�M2�R1)<br />

<strong>Design</strong> actions, V' d � 1.0 � 30000 � 30000 kN<br />

<strong>and</strong> H' d � 1.3 � 1500 � 1950 kN<br />

Eccentricity of loading � 1950(35.0 � 13.7)/30000 � 3.2 m<br />

Width of equivalent block foundation � 10.4 � 2 � 3.2 � 4.0 m<br />

Dimensions of equivalent block foundation are 13.0 � 4.0 � 7.7 m deep<br />

The material factor, � cu, for set M2 is 1.4 <strong>and</strong> R1 is 1.0<br />

<strong>Design</strong> unit resistance to bearing failure 136 � 5.2 � 0.9 � 1.3 � 0.86 � 711.6 kN/m 2<br />

<strong>Design</strong> resistance of foundation � R cd � 711.6 � 13.0 � 4.0 � 37000 kN which is<br />

greater than V' d of 30000 kN<br />

DA1 is used to check compliance with EC7 with respect to sliding. In the following<br />

calculations the passive resistance of the soil to horizontal movement of the piles has been<br />

ignored.<br />

For DA1, combination 1, the base area of the equivalent block using the factored values<br />

of V' <strong>and</strong> H' is 13.0 � 3.1 � 40.3 m 2 . From Table 4.2, M1 is 1.0 <strong>and</strong> R1 for spread<br />

foundations in respect of sliding is 1.0. Therefore design resistance to sliding � 190 � 1.0 �<br />

1.0 � 40.3 � 7657 kN which is greater than H' d � 1.5 � 1500 � 2250 kN.<br />

For DA1, combination 2, base area � 13.0 � 4.0 � 52.0 m 2 , R cd � 1.0 � 136 � 52.0 �<br />

7072 kN which is greater than H� d � 1950 kN.<br />

It is also necessary to confirm that the total settlements <strong>and</strong> tilting of the structure are<br />

within safe limits. The following calculations are carried out using unfactored loadings to<br />

verify the serviceability limit-state.<br />

Calculating first the immediate <strong>and</strong> consolidation settlements under dead <strong>and</strong> imposed<br />

load, but excluding the wind load. Because the piles have under-reamed bases which carry<br />

the major proportion of the load, the base of the equivalent raft will be close to pile base<br />

level. The approximate overall dimensions of the equivalent raft outside the toes of the pile<br />

bases are 13.8 � 11.2 m. Therefore<br />

overall base pressure beneath raft �<br />

<strong>Pile</strong>s to resist uplift <strong>and</strong> lateral loading 371<br />

30 000<br />

13.8 � 11.2 � 194 kN/m 2<br />

Assume a value of E u for the glacial clay of 80 mN/m 2 <strong>and</strong> a value of m v of 0.05 m 2 /kN.<br />

From Figure 5.20 for L/B � 13.8/11.2 � 1.2, H/B ��<strong>and</strong> D/B � 7.7/11.2 � 0.69 (ignoring