Regardless of the materials, framed buildings per<strong>for</strong>m best when<br />

column spacing is limited <strong>and</strong> the use of transfer girders is limited.<br />

Bearing wall systems that rely on interior cross-walls will<br />

benefit from periodically spaced longitudinal walls that enhance<br />

stability <strong>and</strong> control the lateral progression of damage. Bearing<br />

wall systems that rely on exterior walls will benefit from periodically<br />

spaced perpendicular walls or substantial pilasters that limit<br />

the extent of wall that is likely to be affected.<br />

Free-st<strong>and</strong>ing columns do not have much surface area; there<strong>for</strong>e,<br />

air-blast loads on columns are limited by clear-time effects<br />

in which relief waves from the free edges attenuate the reflected<br />

intensity of the blast loads. Where the exterior façade inhibits<br />

clear-time effects prior to façade failure, the columns will receive<br />

the full intensity of the reflected blast pressures. Large st<strong>and</strong>-off<br />

explosive threats may produce large inelastic flexural de<strong>for</strong>mations<br />

that could initiate P- induced instabilities. Short st<strong>and</strong>-off<br />

explosive threats may cause shear, base plate, or column splice<br />

failures. Near contact threats may cause brisance, which is the<br />

shattering of rein<strong>for</strong>ced concrete sections. Confinement of rein<strong>for</strong>ced<br />

concrete members by means of spiral rein<strong>for</strong>cement, steel<br />

jackets, or carbon fiber wraps may improve their resistance. Encasement<br />

of steel sections will inhibit local flange <strong>and</strong> web plate<br />

de<strong>for</strong>mations that could precipitate a section failure. Exterior<br />

column splices should be located as high above grade level as<br />

practical <strong>and</strong> match the capacity of the column section.<br />

Load-bearing walls do not benefit from clear-time effects as columns<br />

do <strong>and</strong> there<strong>for</strong>e collect the full intensity of the reflected<br />

blast pressure pulse. Nevertheless, rein<strong>for</strong>ced concrete loadbearing<br />

walls are particularly effective if adequately rein<strong>for</strong>ced.<br />

Fully grouted masonry walls, on the other h<strong>and</strong>, are more brittle<br />

<strong>and</strong> seismic levels of rein<strong>for</strong>cement greatly increase the ductility<br />

<strong>and</strong> per<strong>for</strong>mance of masonry walls. Continuous rein<strong>for</strong>ced bond<br />

beams, with a minimum of one #4 bar or equivalent, are required<br />

in the wall at the top <strong>and</strong> bottom of each floor <strong>and</strong> roof level. Interior<br />

horizontal ties are required in the floors perpendicular to<br />

the wall. The ties are equivalent to a #4 bent bar at a maximum<br />

2-2 Structural deSign criteria