In a bathroom, drain traps <strong>for</strong> the sink, tub, shower, or floor are<br />

usually filled with water, but should be checked to ensure water is<br />

present to prevent air leakage through the drain pipes.<br />

A window-type or through-the-wall air conditioner can be sealed<br />

by turning it off, <strong>and</strong> placing either contact paper or plastic<br />

sheeting with duct tape over the air conditioner.<br />

3.4.1.3 Preparing <strong>for</strong> Deactivation of Fans. Some safe room systems<br />

have been designed with the capability to automatically<br />

deactivate all fans in the building with a single switch. This singleswitch<br />

control can also be designed to close dampers in outside-air<br />

ducts serving the safe room. The low-cost alternative to automatic<br />

fan shutoff is to record on a checklist the location of switches <strong>for</strong><br />

all fans in the building, not just those that serve the safe room.<br />

This includes air-h<strong>and</strong>ling units, exhaust fans, supply fans, window<br />

air conditioners, <strong>and</strong> combustion heaters.<br />

This checklist must also include the procedures <strong>for</strong> the purging<br />

step of sheltering-in-place (e.g., opening windows <strong>and</strong> doors, <strong>and</strong><br />

turning on fans <strong>and</strong> air h<strong>and</strong>lers that were turned off to shelter-inplace<br />

after the hazardous condition has passed).<br />

3.4.1.4 Accommodating Air Conditioning <strong>and</strong> Heating. Conventional<br />

air conditioning <strong>and</strong> heating systems must not be operated<br />

in the protective mode because the fans directly or indirectly introduce<br />

outside air. This includes the air-h<strong>and</strong>ling units <strong>and</strong> fans<br />

serving spaces outside the safe room. An exception is combustion<br />

heaters of hydronic systems that are located in separately ventilated<br />

mechanical rooms.<br />

In extreme weather conditions, however, confining people in a<br />

sealed room without air conditioning or heating can result in intolerable<br />

conditions, causing people to exit the safe room be<strong>for</strong>e<br />

it is safe to do so.<br />

The mechanical ventilation system often has a higher potential<br />

<strong>for</strong> indoor-outdoor air exchange than the leakage paths of the<br />

3- CBR ThReaT pRoTeCTion