3.5 opeRaTionS anD MainTenanCe<br />

For a shelter to be successful, it is critical to have an underst<strong>and</strong>ing<br />

<strong>and</strong> dedication to operations <strong>and</strong> maintenance.<br />

Depending on the shelter type, specific operations instructions<br />

<strong>and</strong> maintenance are needed.<br />

m Instructions <strong>and</strong> checklists. As a minimum <strong>for</strong> operating<br />

procedures, the condensed operating <strong>and</strong> maintenance<br />

instructions should be posted in each safe room. The<br />

operating instructions should explain the steps of placing the<br />

safe room into operation <strong>and</strong> may be as simple as a one-page<br />

typed checklist; instructions that should be included are safe<br />

room operating procedures, a list of doors to be secured, a<br />

list of switches <strong>for</strong> fans to be turned off, stations/channels <strong>for</strong><br />

emergency instructions, emergency phone numbers, <strong>and</strong> dates<br />

by which filters should be changed, if applicable.<br />

m Status indicators. For safe rooms that require multiple<br />

automatic dampers to isolate the safe room from the HVAC<br />

ducts in the protective mode, status lights <strong>and</strong>/or visual<br />

indicators should be used to show the position of each damper.<br />

Indicators can also be used to show door position, if there are<br />

multiple boundary doors in the safe room. Each status light<br />

should be marked with a reference number corresponding to<br />

a diagram so an operator can easily determine the location of<br />

any damper/door <strong>and</strong> conduct troubleshooting if problems<br />

occur. The indicator lights should have push-to-test capability<br />

<strong>for</strong> the light bulbs of the status lights.<br />

m Public-address system. For safe rooms in large buildings,<br />

a public address system is the most efficient means of<br />

instructing building occupants to proceed to a safe room in<br />

an emergency. Telephone or audible alarm systems can also<br />

be used, but they are less efficient than a broadcast voice<br />

system. Communications systems (telephone, alarm, <strong>and</strong> mass<br />

notification systems) should be tied to emergency phone<br />

systems. Non-verbal warning systems are generally less effective<br />

CBR ThReaT pRoTeCTion<br />

3- 3