Figure 3-<br />

automatic dampers are<br />

used to isolate the safe<br />

room from the ducts or<br />

vents used in normal hVaC<br />

system operation.<br />

SoURCe: ChemiCal SToCkpile<br />

emeRgenCy pRepaRedneSS<br />

pRogRam<br />

m Heating system safety. If a fuel-fired indirect heater (i.e.,<br />

heat exchanger) is used to heat the safe room, a carbon<br />

monoxide detector with a visual display <strong>and</strong> an audible alarm<br />

should be installed in the safe room. Electric coil <strong>and</strong> hotwater<br />

coil systems do not require a carbon monoxide detector.<br />

m Pressure gauge. For Class 1 <strong>Safe</strong> <strong>Rooms</strong>, the pressure gauge<br />

is the indicator that the system is operating properly. This<br />

gauge displays the pressure in the safe room relative to<br />

outdoors or outside the safe room indoors. If the reference<br />

pressure is measured indoors, the readings can be subject<br />

to variations caused by fan pressures unless other building<br />

heating, ventilation, <strong>and</strong> air conditioning (HVAC) fans are<br />

turned off when the safe room is in use. Reading the reference<br />

pressure outdoors can be subject to positive <strong>and</strong> negative<br />

variations caused by air flows over <strong>and</strong> around the building. If<br />

the pressure sensor is outdoors, it should be shielded from the<br />

wind. Indoors is the best location if the building HVAC fans<br />

are turned off when the safe room is in use.<br />

3- CBR ThReaT pRoTeCTion