Relief Damper. In supplying filtered air from the top of the stairwell,<br />

the carbon dioxide concentration in the occupied stairwell<br />

increases with the vertical distance from the source of fresh air,<br />

because leakage paths are evenly distributed along the vertical<br />

axis. To ensure carbon dioxide levels remain within safe limits at<br />

the lowest levels of the stairwell <strong>and</strong> to facilitate removal of heat<br />

<strong>and</strong> humidity generated by the occupants, a relief damper was<br />

installed at the lowest level to maximize the flow-path length <strong>for</strong><br />

clean air. The relief damper was adjusted to prevent the internal<br />

pressure from exceeding 0.30 iwg, a pressure above which the<br />

doors that open into the stairwell could require more than 30<br />

pounds of <strong>for</strong>ce at the door h<strong>and</strong>le to open (depending upon<br />

door closer <strong>for</strong>ce).<br />

Door Seals. Weather-type seals were installed on doors into the<br />

stairwell to minimize air leakage around the closed doors. According<br />

to blower door test results, leakage around the stairwell<br />

doors be<strong>for</strong>e the addition of weather-stripping <strong>and</strong> wipe seals was<br />

substantial (approximately 3,000 cfm at 0.3 iwg).<br />

Warning System. A public address system was installed in the<br />

building so that voice messages could be broadcast throughout<br />

the building to notify people at any location of an emergency.<br />

Accessibility. The stairwell offers a point of entry accessible to<br />

wheelchairs, <strong>and</strong> each l<strong>and</strong>ing provides an area adequate <strong>for</strong> two<br />

wheelchairs without blocking access to the door.<br />

Drinking Water. The stairwell has no accommodation <strong>for</strong> drinking<br />

water. There were plans to make water available by storing bottled<br />

water in a compartment on each l<strong>and</strong>ing of the stairwell.<br />

Communications. Each level of the stairwell has an emergency<br />

telephone <strong>and</strong> an intercom to provide contact with the security<br />

operations center.<br />

Cost. Total cost of the installed system was $190,000, or about $300<br />

per person sheltered. This does not include the cost of the public<br />

3- CBR ThReaT pRoTeCTion