Task 4. Determine How Much Filtered Air Flow is Required<br />

The total filtered, ventilation air flow required is the larger of:<br />

(1) the flow rate required <strong>for</strong> pressurization <strong>and</strong> (2) the flow rate<br />

required to supply greater than 5 cfm of outside air per person in<br />

the safe room. At a maximum safe room occupancy of 600 people,<br />

the 5 cfm/person ventilation requirement is met with a flow rate<br />

of 3,000 cfm. Using a filter unit of 4,000 cfm capacity yields a ventilation<br />

rate greater than 5 cfm per person. This ventilation flow<br />

rate is not adequate; however, to deliver the cooling required <strong>for</strong><br />

the heat load of the fully occupied stairwell, two fan-coil units are<br />

added to the lower levels <strong>for</strong> additional cooling.<br />

Task 5. <strong>Design</strong> <strong>and</strong> Install the System<br />

<strong>Design</strong> <strong>and</strong> installation requires a licensed mechanical contractor<br />

with experience in the installation of high-efficiency<br />

filtration systems.<br />

The safe room requires the following components installed in<br />

the stairwell <strong>and</strong> a penthouse mechanical room adjacent to the<br />

stairwell:<br />

m Air-filtration unit <strong>and</strong> supply fan of 4,000-cfm capacity<br />

m Pre-heat coil cabinet containing pre-filters, heating coils, <strong>and</strong><br />

isolation damper<br />

m Cooling-coil cabinet containing coils <strong>and</strong> an isolation damper<br />

m Spiral ductwork<br />

m Control panel with pressure gauge <strong>and</strong> system status lights<br />

m Remote on/off switch connected via the building automation<br />

system<br />

m Pressure relief damper at the lowest level of the stairwell<br />

m Supply register at the top level of the stairwell<br />

m Pressure sensor <strong>and</strong> thermostats installed in the stairwell<br />

m Weather stripping <strong>and</strong> wipe seals on doors into the stairwell<br />

CBR ThReaT pRoTeCTion<br />

3-3