Table 1-4: ISC CBR Levels of Protection<br />

Level of<br />

Protection<br />

Low<br />

Medium<br />

High<br />

For Biological/<br />

Radiological<br />

Contaminants<br />

use minimum<br />

efficiency reporting<br />

value (MerV) 13<br />

filter or functional<br />

equivalent.<br />

use high-efficiency<br />

particulate air (HePa)<br />

filter or functional<br />

equivalent.<br />

use HePa filter or<br />

functional equivalent.<br />

For<br />

Chemical/<br />

Radiological<br />

Additional Considerations Class<br />

none none 3<br />

use gas<br />

absorber <strong>for</strong><br />

outside air.<br />

use gas<br />

absorber <strong>for</strong><br />

outside air<br />

<strong>and</strong> return<br />

air.<br />

design <strong>for</strong> future detection<br />

technology<br />

stairway pressurization<br />

system should maintain<br />

positive pressure in stairways<br />

<strong>for</strong> occupant refuge, safe<br />

evacuation, <strong>and</strong> access<br />

by firefighters. the entry<br />

of smoke <strong>and</strong> hazardous<br />

gases into stairways must be<br />

minimized.<br />

Locate utility systems at least<br />

1 m ( 0 ft) from loading<br />

docks, front entrances, <strong>and</strong><br />

parking areas.<br />

design <strong>for</strong> future detection<br />

technology<br />

stairway pressurization<br />

system should maintain<br />

positive pressure in stairways<br />

<strong>for</strong> occupant refuge, safe<br />

evacuation, <strong>and</strong> access<br />

by firefighters. the entry<br />

of smoke <strong>and</strong> hazardous<br />

gases into stairways must be<br />

minimized.<br />

Locate utility systems at least<br />

1 m ( 0 ft) from loading<br />

docks, front entrances, <strong>and</strong><br />

parking areas.<br />

1-18 design considerations<br />