3.1 oVeRVieW<br />

This chapter describes how to add CBR protection capability<br />

to a shelter or safe room.<br />

CBR ThReaT pRoTeCTion<br />

CBR THReaT pRoTeCTion 3<br />

A CBR safe room protects its occupants from contaminated<br />

air outside it by providing clean, breathable air in two ways: (1)<br />

by trapping air inside the room <strong>and</strong> minimizing the air exchange<br />

(an unventilated safe room) <strong>and</strong> (2) by passing contaminated air<br />

through a filter to purify it as it is supplied to the room (a ventilated<br />

safe room).<br />

Unventilated safe rooms that are tightly sealed cannot be occupied<br />

<strong>for</strong> long periods without the risk of high carbon dioxide<br />

levels. This constraint does not apply to ventilated safe rooms,<br />

which can be designed to provide filtered <strong>and</strong> conditioned fresh<br />

air at any desired rate. Ventilated safe rooms can there<strong>for</strong>e be<br />

used on a routine basis, although most are designed as st<strong>and</strong>by systems,<br />

not <strong>for</strong> continuous, routine use.<br />

Obtaining protection from an unventilated safe room can be as<br />

simple as selecting a relatively tight room, entering it, <strong>and</strong> closing<br />

the door. This procedure is commonly referred to as expedient<br />

sheltering-in-place. In this simple <strong>for</strong>m, a safe room protects its<br />

occupants by retaining a volume of clean air <strong>and</strong> minimizing the<br />

infiltration of contaminated outdoor air. In practice, however, a<br />

safe room is not perfectly tight. The natural <strong>for</strong>ces of wind <strong>and</strong><br />

buoyancy act on small, distributed leakage paths to exchange air<br />

between the inside <strong>and</strong> outside.<br />

As contaminated air infiltrates a safe room, the level of protection<br />

to the occupants diminishes with time. With infiltration in a sustained<br />

exposure, the concentration of toxic vapor, gas, or aerosol<br />

in the safe room may actually exceed the concentration outdoors<br />

because the sealed safe room tends to retain the airborne<br />

3-