Output characteristics at various power factors<br />

kW/kVA<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

PMC 200: (40 kW)<br />

– 0.85<br />

Rittal IT catalogue/Power<br />

– 0.90<br />

cap.<br />

Power<br />

Technical specifications<br />

– 0.95 1.00 0.95 0.90 0.85 0.80 0.75<br />

cosphi. ind.<br />

4. Standards<br />

Safety EN 62 040-1-1: 2003, EN 60 950-1: 2006<br />

EMC<br />

2006, EN 61 000-3-2: 2000, EN 61 000-3-3: 2006,<br />

EN 61 000-6-2: 2006, EN 61 000-6-4: 2002<br />

Classification code VFI SS 111 EN 62 040-3: 2002<br />

Product conformity CE<br />

Protection rating IP 20<br />

5. General technical specifications<br />

Module range Up to 100 kW Up to 200 kW<br />

Module types 10 15 20 25 30 40 50<br />

Noise level at 100 %/50 % load dB (A) 55/49 57/49 57/49 57/49 59/51 63/53 63/53<br />

Ambient temperature UPS °C 0 – 40<br />

Ambient temperature for batteries (recommended) °C 20 – 25<br />

Storage temperature °C –25 to +70<br />

Battery storage time at ambient temperature Max. 6 months<br />

Max. height (above sea level) 1000 m (3300 ft) without de-rating (max. 3000 m (10000 ft))<br />

Relative humidity Max. 95 % (non-condensing)<br />

Accessibility<br />

Total accessibility from the front for servicing and maintenance<br />

(side, no access required from the roof or rear)<br />

Siting Min. 20 cm spacing from the wall (required for cooling)<br />

Input and output wiring. From the front, below<br />

Efficiency AC – AC<br />

at 100 %/75 %/50 %/25 % load (cosphi 1.0)<br />

% 96/95/95/95<br />

Eco-mode efficiency at 100 % % 98<br />

kVA<br />

kW<br />

109<br />

Power