Rittal IT News/Security<br />

CMC-TC leak sensor, 15 m<br />

The leak sensor is able to detect electrically<br />

conductive fluids such as freshwater, salt water,<br />

glycol solutions etc. over a distance of 15 m. The<br />

sensor may be fitted underneath water pipelines,<br />

LCP applications, climate control applications in<br />

bayed enclosure suites etc., preferably on the<br />

floor. Attachment on or close to the floor allows<br />

the system to detect even tiny quantities of fluid.<br />

The sensor may be connected directly to the<br />

I/O Unit using the patch cable supplied loose via<br />

plug & play. The sensor contains an identifier<br />

allowing it to be automatically detected and set up<br />

by the CMC-TC system.<br />

The 15 m long sensor cable is connected to an<br />

enclosure with the evaluation electronics via a<br />

3.5 m long connection cable. The enclosure must<br />

be correctly installed according to the IP protection<br />

category, e.g. in a Rittal rack. The sensor<br />

cable is colour-coded to distinguish it from other<br />

cables in the monitoring area. The carrier material<br />

PEHD is chemically neutral with long-term stability.<br />

The PHLD sensor cable is very robust and<br />

protects the measurement wires inside from damage<br />

and accidental activation. The sensor cable is<br />

liquid-repelling and can therefore be quickly<br />

reused following a leak.<br />

CMC-TC acoustic antivandalism<br />

sensor<br />

The CMC-TC acoustic sensor may be used in all<br />

situations where protection from vandalism is<br />

required. The sensor responds to loud mechanical<br />

noises such as those associated with a breakin.<br />

The sensitivity of the sensor is adjustable. The<br />

sensor contains an identifier allowing it to be automatically<br />

detected and set up by the CMC-TC<br />

system.<br />

Security<br />

Accessories for the CMC-TC system<br />

Model No. DK<br />

Leak sensor 7320.631<br />

Extended delivery times.<br />

To fit sensor unit:<br />

I/O Unit<br />

<br />

Access Unit Climate Unit<br />

Technical specifications:<br />

Monitoring: Conductive sensor cable<br />

Length of sensor cable: 15 m<br />

Connection cable to electronics: 3.5 m<br />

Patch cable to I/O Unit: 2 m<br />

Rated voltage: 24 V DC<br />

Protection category of electronics with enclosure:<br />

IP 40 to EN 60 529<br />

Temperature range: +5°C to +45°C<br />

Model No. DK<br />

Acoustic sensor 7320.640<br />

Extended delivery times.<br />

To fit sensor unit:<br />

I/O Unit<br />

<br />

Access Unit Climate Unit<br />

Technical specifications:<br />

Sensor: Microphone<br />

Frequency range: 50 Hz – 10 kHz<br />

Noise level: 60 – 100 dB (A)<br />

Response time: 20 ms<br />

Patch cable to I/O Unit: 2 m<br />

Rated voltage: 24 V DC<br />

Protection category of electronics with enclosure:<br />

IP 40 to EN 60 529<br />

Temperature range: +5°C to +45°C<br />