Engineering and consultancy<br />

Engineering and consultancy<br />

UPS<br />

1. VFD-UPS, old: Off-line (standby) UPS<br />

Functional description:<br />

In undisturbed operation, the current is<br />

conveyed from the mains to the connected<br />

devices (computers) by the UPS with no<br />

voltage conversion. Parallel to this, the batteries<br />

are charged via a rectifier. If voltage<br />

fluctuations or power failures occur, the offline<br />

UPS automatically switches to battery<br />

mode, and from the energy in the batteries a<br />

supply voltage is formed via the inverter. The<br />

changeover to battery mode occurs within<br />

approx. 2 – 4 ms, i.e. virtually without interruption.<br />

Protection from:<br />

● Power failure/mains failure<br />

● Voltage drop/voltage dip<br />

● Voltage surges<br />

1<br />

1 Mains<br />

2 Rectifier<br />

3 Inverter<br />

4 Changeover switch<br />

5 Battery<br />

6 Equipment<br />

2. VI-UPS, old: Line-interactive UPS (off-line UPS + AVR)<br />

Functional description:<br />

Unlike the off-line UPS the line-interactive<br />

UPS offers a more stable output voltage,<br />

thanks to the additional use of an AVR unit<br />

(automatic voltage regulator).<br />

Protection from:<br />

● Power failure/mains failure<br />

● Voltage drop/voltage dip<br />

● Voltage surges<br />

● Undervoltage<br />

● Overvoltage<br />

1<br />

1 Mains<br />

2 Rectifier<br />

3 Inverter<br />

4 Changeover switch<br />

5 Battery<br />

6 Equipment<br />

~/= =/~<br />

416 Rittal IT catalogue/Engineering/Consultancy<br />

2<br />

2<br />

5<br />

AVR<br />

Application area:<br />

● PCs and peripheral devices<br />

● Emergency lights<br />

● Small TC installations<br />

~/= =/~<br />

5<br />

3<br />

Normal operation<br />

In case of mains failure<br />

Application area:<br />

● PCs and small servers<br />

● Larger telecommunications systems<br />

● Smaller server systems and networks<br />

3<br />

Normal operation<br />

In case of mains failure<br />

4<br />

4<br />

6<br />

6