Masoneilan SVI II AP Installation and Maintenance ... - GE Energy
Masoneilan SVI II AP Installation and Maintenance ... - GE Energy
Masoneilan SVI II AP Installation and Maintenance ... - GE Energy
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>GE</strong> Oil <strong>and</strong> Gas<br />
<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />
CALIBration Menu<br />
CAUTION: These functions stroke the valve over its full range.<br />
Do not perform while the valve is controlling the process.<br />
CALIB<br />
*<br />
STOPS<br />
*<br />
RUNNING<br />
*<br />
+ + + + +<br />
+<br />
TUNE<br />
SETUP<br />
STOP OP<br />
SIG LOW SIG HIGH<br />
*<br />
*<br />
*<br />
*<br />
*<br />
*<br />
*<br />
*<br />
<br />
STEP 1/3 +/- <br />
+/-<br />
+/-<br />
+/- CALIB<br />
* - +<br />
*<br />
* - +<br />
* - +<br />
STEP 2/3<br />
*<br />
STEP 3/3<br />
*<br />
*<br />
FAILURE<br />
If there is a calibration stops error<br />
FAILURE displays. Press * briefly <strong>and</strong><br />
automatically return to the start of STOPS.<br />
FAILURE<br />
If there is a calibration tuning error<br />
FAILURE displays. Press * briefly <strong>and</strong><br />
automatically return to the start of TUNE.<br />
Figure 60<br />
Calibration Pushbutton Guide<br />
100