Calibration Menu<br />
The Calibration menu shown in Figure 54 provides access to all the calibration functions<br />
for the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>. If a change is made in the Air-To-Open/Air-To-Close configuration option<br />
or if you move the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> to a different valve or make any change to the valve position<br />
linkage, you must run the find STOPS calibration again.<br />
CALIBration Menu<br />
CAUTION: These functions stroke the valve over its full range.<br />
Do not perform while the valve is controlling the process.<br />
CALIB<br />
*<br />
STOPS<br />
*<br />
RUNNING<br />
*<br />
+ + + + +<br />
+<br />
TUNE<br />
SETUP<br />
STOP OP<br />
SIG LOW SIG HIGH<br />
*<br />
*<br />
*<br />
*<br />
*<br />
*<br />
*<br />
*<br />
<br />
* - +<br />
STEP 1/3 +/-<br />
+/-<br />
*<br />
<br />
+/-<br />
+/- CALIB<br />
* - +<br />
* - +<br />
STEP 2/3<br />
*<br />
STEP 3/3<br />
*<br />
*<br />
FAILURE<br />
If there is a calibration stops error<br />
FAILURE appears. Press * briefly <strong>and</strong><br />
automatically return to the start of STOPS.<br />
FAILURE<br />
If there is a calibration tuning error<br />
FAILURE appears. Press * briefly <strong>and</strong><br />
automatically return to the start of TUNE.<br />
Figure 54<br />
CALIBration Menu<br />
80