14.11.2013 Views

Masoneilan SVI II AP Installation and Maintenance ... - GE Energy

Masoneilan SVI II AP Installation and Maintenance ... - GE Energy

Masoneilan SVI II AP Installation and Maintenance ... - GE Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>GE</strong> Oil <strong>and</strong> Gas<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

Tight Shutoff<br />

Configuring TS ON<br />

Turning TS OFF<br />

Changing Language<br />

Tight Shutoff is an optional performance feature that prevents leakage at the closed<br />

position. Without this feature, at the closed position with an input signal of 0%, the valve<br />

may be forced tight against the seat with maximum available actuator force or it may be<br />

only touching the seat with minimum force. In either case, it is under control.<br />

To prevent leakage that can occur in the second case, configure TS ON <strong>and</strong> set a value<br />

of position setpoint below which the actuator applies maximum seating force. As the<br />

position signal drops toward the TS value, <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> moves the valve to the TS position<br />

value. When the position reaches the TS value <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> applies maximum actuator<br />

force.<br />

The TS function has 0.5% deadb<strong>and</strong> to prevent chatter. If TS is set ON at 2%, for<br />

example, then the valve begins to open when the setpoint reaches 2.5%.<br />

1. Press * to turn TS ON.<br />

2. Press + to increase TS.<br />

3. Press - to decrease TS.<br />

4. Press * when finished to return to the CONFIG menu.<br />

The CONFIG menu displays TS ON.<br />

1. Press * to turn TS OFF.<br />

2. Press + to continue scrolling through the menu.<br />

The local display language can be English or French.<br />

1. Press * to toggle from ENGLISH to FRANCAIS.<br />

2. Press + to continue to scroll through Config menu.<br />

78