Adjust Input Signal Range<br />

Configuration <strong>and</strong> Calibration<br />

Adjust Input Signal Range<br />

SIG LO displays the input signal that corresponds to the full closed (ATO) or full open<br />

(ATC) position of the valve.<br />

1. If the displayed value is:<br />

Correct, press + to advance to the next item.<br />

Not correct, press * to display value of SIG LO.<br />

2. Use + <strong>and</strong> – buttons to change the value.<br />

3. Press * to return to menu <strong>and</strong> move to next item. SIG LO must be between 3.8 <strong>and</strong><br />

14.0 mA.<br />

SIG HI displays the input signal that corresponds to the full open, ATO, or full<br />

closed, ATC position.<br />

4. If the displayed value is:<br />

Correct, press + to advance to the next item.<br />

Not correct, press * to display value of SIG HI.<br />

5. Use + <strong>and</strong> – buttons to change the value.<br />

6. Press * to return to menu <strong>and</strong> move to next item. SIG HI must be between 10.0 <strong>and</strong><br />

20.2 mA. SIG HI must be larger than SIG LO by at least 5 mA.<br />

Calibration of the positioner is now complete.<br />

7. At -› MAN, press * to return to the MANUAL mode. MAN POS appears.<br />

NOTE<br />

SIG HI <strong>and</strong> SIG LO allow adjustment of the input current<br />

range that corresponds to full valve travel. Normally they are<br />

set to 4 <strong>and</strong> 20 mA. Adjustment is normally required only for<br />

split range applications <strong>and</strong> provides flexibility for unusual<br />

applications. A separate ValVue calibration procedure<br />

enables adjustment of the current sensing circuit to a<br />

precision current reference st<strong>and</strong>ard.<br />

99